FormOrion-OE521XX-M-RndDmpr-Sub-01G

Page

1 of 2


Description

The OE521-XX-M Round Pressure
Independent Zone Damper Assembly with
modular connectors consists of a round
air damper with air flow pickup cross and
a Zone Controller Actuator Package
(including air flow sensor) with modular
connectors. An optional Zone Controller
Expansion Module (OE325-01) is
available for control of reheat, heat and/or
control of series or parallel flow fan
terminal units.

The Zone Controller board is
microprocessor based and communicates
with the HVAC unit controller on the Orion
network communications loop. The Zone
Controller monitors the space
temperature and allocates the proper
airflow into its assigned space to achieve
the desired comfort and ventilation levels.

Pressure Independent Zone Dampers are
used in air conditioning systems require
pressure independent airflow control. If
your system requires pressure dependent
control of the airflow, see the “OE520-XX-M Round Pressure Dependent Zone Damper” submittal sheet for the
correct specifications. All dampers are tested for performance in accordance with AMCA 500D standards.

Mounting

The Zone Damper Assembly should be mounted according to standard duct installation practices with airflow
direction as shown in the illustration above. After installation of the Zone Damper in the ductwork, insulation
should be applied around any remaining un-insulated surface on the damper inlet and outlet. The Zone Damper
should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control
enclosure in a vertical plane. Do not mount the Zone Damper Assembly with the control enclosure on the top or
bottom of the ductwork. Adequate clearance should be maintained between the control panel and any
obstruction to allow for removal of the control panel cover and access to the controls.



OE521-XX-M Round P.I.

Zone Damper

Assembly W/ Modular Connectors

Technical Data

OE521-XX-M Round Pressure Independent

Zone Damper Assembly W/ Modular Connectors

Zone Controller:

Air Damper Construction:

Supply Power

24 Volt AC

Damper Body

20 Ga. Galv. Steel

Power Consumption

6 VA Maximum

Damper Blade

Round -18 Ga. Galv. Steel

Operating Temperature

35

F to 125F

Damper Bearings

Stainless Steel

Operating Humidity

90% RH Non-Condensing

Damper Seal

EPDM Rubber Gasket

Communications

RS-485 - 9600 Baud

Leakage

< 20 CFM Per Sq. Ft. @ 4” SP

Inputs:

Insulation

½” Foil Faced Fiberglass

Air Flow Sensor

Dimensions:

Room Temperature Sensor

Air Damper Model

“A”

“B”

“C”

Setpoint Adjustment

OE510-06 (6”)

23.00

5.88

9.88

Actuator Position Feedback

OE510-08 (8”)

23.00

7.88

12.13

Communication Connectors:

Modular In & Out

OE510-10 (10”)

23.00

9.88

14.31

Outputs:

OE510-12 (12”)

23.00

11.88

16.43

Expansion Port for Auxiliary Relay Board

OE510-14 (14”)

23.00

13.88

18.50

Actuator Port for Connection to Damper Actuator

OE510-16 (16”)

23.00

15.88

20.56

WattMaster reserves the right to change specifications without notice

Three Year Warranty On Electronic Components

One Year Warranty On Air Damper