Form: Orion-OE523-RdSlaveDmpr-Sub-01F

Page

1 of 2

Description

The OE523-XX Round Slaved Zone
Damper Assembly, consists of a round air
damper, actuator, (1) slave wiring interface
card mounted in the enclosure and also
includes (1) slave wiring interface card kit
shipped loose for field mounting to the
master zone damper assembly. This kit
contains a slave wiring interface card and a
cable.

The Round Slaved Zone Damper
Assembly is used in systems when it is not
possible or practical to use a single large
Zone Damper to satisfy the zone's CFM
requirements.

A total of two Slaved Zone Dampers may
be used in conjunction with a master Zone
Damper. The Slave Damper(s) are wired in
parallel with the master Zone Damper and
track the movement of the master Zone
Damper. Connection of the master Zone
Damper requires a slave wiring interface
kit, which is shipped loose for field
mounting to the master Zone Damper and
is supplied with each Slaved Zone
Damper. The kit connects the Zone
controller on the master to the master
actuator and provides wiring terminals for
wiring to the Slaved Zone Dampers. Only (1) of these kits is required for each master/slave installation. All
dampers are tested for performance in accordance with AMCA 500D standards.

Mounting

The Slaved Zone Damper Assembly should be mounted according to standard duct installation practices with air
flow direction as shown in the illustration above. After installation of the Air Damper in the ductwork, insulation
should be applied around any remaining un-insulated surface on the air valve inlet and outlet. The Air Damper
should be mounted so the control enclosure is positioned to the left or right side of the ductwork with the control
enclosure in a vertical plane. Do not mount the Air Damper Assembly with the control enclosure on the top or
bottom of the ductwork. Adequate clearance should be maintained between the control panel and any
obstruction to allow for removal of the control panel cover and access to the controls.

OE523-XX Round Slaved Zone

Damper Assembly


Technical Data

OE523-XX Round Slaved

Zone Damper Assembly

Actuator:

Air Damper Construction:

Supply Power

24 Volt AC

Damper Body

20 Ga. Galv. Steel

Power Consumption

3.4 VA Maximum

Damper Blade

Round -18 Ga. Galv. Steel

Operating Temperature

35

°F to 125°F

Damper Bearings

Stainless Steel

Operating Humidity

90% RH Non-Condensing

Damper Seal

EPDM Rubber Gasket

Position Feedback (Bypass)

10Kohm, 1 W Potentiometer

Leakage

< 20 CFM Per Sq. Ft. @ 4” SP

Insulation

½” Foil Faced Fiberglass

Dimensions:

Air Damper Model

“A”

“B”

“C”

Air Damper Model

“A”

“B”

“C”

OE513-06 (6”)

23.00

5.88

9.88

OE513-12 (12”)

23.00

11.88

16.43

OE513-08 (8”)

23.00

7.88

12.13

OE513-14 (14”)

23.00

13.88

18.50

OE513-10 (10”)

23.00

9.88

14.31

OE513-16 (16”)

23.00

15.88

20.56

WattMaster reserves the right to change specifications without notice

Three Year Warranty On Electronic Components

One Year Warranty On Air Damper