Description, Applications – Orion System OE742-XX-VAVZ User Manual

Page 29

Advertising
background image




Form: ORION-OE281-04-ProportionalDamper Actuator-1D.doc

Page

1 of 1

Description

The OE281-04 Proportional Control
Damper Actuator is a shaft mounted, di-
rect coupled actuator. The Damper Ac-
tuators utilize a 24VAC/24VDC power
supply. Wiring connection to the actua-
tor is by means of screw wiring termi-
nals located on the actuator cover. The
actuator is rated for 35 in-lb of torque.
All actuators are electronically protect-
ed against overload. The angle of rota-
tion is mechanically limited to 95

.

When the end position of the actuator
or damper is reached, the actuator au-
tomatically stops. For adjustment pur-
poses, the gears can be manually dis-
engaged by pushing the manual over-
ride button on the actuator cover. A vis-
ual pointer on the actuator indicates the
position of the actuator.

Applications

The OE281-04 Damper Actuator is
used to provide control of bypass air
dampers in an Orion zoning system.
When used in zoning applications with
a bypass damper, it is wired to the air
handling unit controller boards 0-
10VDC analog output.



Technical Data

OE281-04

Damper Actuator

Power Supply

24VAC

 20% 50/60HZ

Angle of Rotation

Max. 95

, Adjustable

Life Cycle Rating

2.5 Million Cycles

with Mechanical Stops

Power Consumption

3 VA Maximum

Power Connection

(4) Screw Wiring Terminals for
26 to 14 Gauge Wire

Operating Temp

-22

F to 122F

Servicing Maintenance

Free

Operating Humidity

5 to 95% RH Non-Condensing

Quality Standard

ISO 9001

Overload Protection

Electronic Throughout 0 to 95

Rotation

Agency Listings

UL873 listed
CSA 4813 02 Certified

Operating Range

2 to 10 VDC

Torque

Minimum 35 in-lb

Running Time

80-110 Seconds.

Weight

1.2 lb.

Three Year Warranty

WattMaster reserves the right to change specifications without notice

OE281-04 – Proportional Control

Damper Actuator

Advertising