VAV/Zone Cable Length Worksheet

Project Name:

_____________________________________________

Local Loop Number:

______________________

Directions: Estimate cable lengths from building mechanical plans and place in estimated cable length column beside each VAV/Zone controller or
Power/Comm board on loop. Select available cable lengths closest to estimated cable lengths and extensions for each controller or Power/Comm
board on list and place checkmarks in these columns. Also Use this information for ordering correct quantity and length of modular or digital cables and
extensions. Total each cable length column on each page and add both page totals together.

Form: Orion-VAVZoneCableEst-All-1A.doc

Page 1 of 2

VAV/Zone

Address

VAV/Zone Controller Or

Power/Comm Board

Description, Location Or

Tag Number

Estimated

Incoming

Power/Comm

Cable

Length

Available

Power/Comm

Cable Length

Estimated

Incoming

Modular Or

Digital Room

Sensor Cable

Length

Available

Modular Or Digital Room

Sensor Cable Length

See Notes Below

3 Ft.

25 Ft.

40 Ft.

80 Ft.

120 Ft.

E-10 Ft.

E-20 Ft.

5 Ft.

10 Ft.

25 Ft.

40 Ft.

80 Ft.

120 Ft.

160 Ft.

N/A

Power Comm Board 1

Caution:
Each Power/Comm board has a total of 4 branch circuits. No more
than 6 modular devices are allowed per branch circuit. No more
than 16 modular devices total can be connected to each
Power/Comm board. The longest total run per branch circuit is 240
Feet.

N/A

Power Comm Board 2

N/A

Power Comm Board 3

N/A

Power Comm Board 4

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

21

22

23

24

25

26



27

28

Page

Totals

Notes:
1.)

Available Power/Comm cable lengths with the prefix “E” (E-10 Ft. or E-20 Ft.) are extensions to be used in conjunction with another standard Power/Comm cable
length to extend it to a desired length, they cannot be used by themselves without connection to a standard cable.


2.)

Available Modular Sensor cable lengths are provided in 5 Ft, 10 Ft., 25 Ft., 40 Ft. and 80 Ft. Lengths. To get longer lengths you can join 2 Modular cables together
using the MS000029 Modular Room Sensor Cable Coupler to extend the cables to a desired length in between or greater than the standard cable sizes. Available
Digital Sensor cable lengths are provided in 5 Ft., 10 Ft., 25 Ft., 40 Ft., 80 Ft., 120 Ft. and 160 Ft. sizes. You can join 2 Modular cables together using the MS000029
Modular Room Sensor Cable Coupler to extend the cables to a desired length in between the available sizes. It is recommended that you avoid this when using the
Digital Sensor cable. The maximum allowable total cable length for Digital Sensor cables is 160 Ft. and should never be exceeded.