Oe521-xx-m round p.i, Zone damper assembly w/ modular connectors, Zone damper sizing – Orion System OE742-XX-VAVZ User Manual

Page 13: Zone damper selection data

Advertising
background image

FormOrion-OE521XX-M-RndDmpr-Sub-01G

Page

2 of 2

Zone Damper Sizing

Use a load program to determine the peak
load for each zone. These calculations will be
used to select Zone Damper sizes.

The Orion Systems utilize a typical low
pressure duct design. To reduce noise
problems, duct pressures should not exceed
1” W.C.

Primary trunk ducts used with Orion systems
should not be “undersized”. This is especially
true of “pressure dependent” systems. With
larger trunk ducts, it is easier to assure
relatively constant pressure to each Zone
Damper. Runs should be as short as
possible, and the trunk duct system kept as
symmetrical as possible to facilitate system
balancing. Wherever possible, run the trunk
ducts above corridors and locate the Zone
Dampers above corridors to reduce the noise
in the space and facilitate service of the
dampers. Trunk ducts should be sized for no
more than 0.1” W.C. drop per 100 ft. of duct,
and a maximum duct velocity of 2000 FPM.

Zone Damper Selection Data

OE521-XX-M Round Pressure Independent Zone Damper

Assembly W/ Modular Connectors

Zone Damper Round Duct Size

(Area Ft

2

)

6”

(0.196)

8”

(0.349)

10”

(0.545)

12”

(0.785)

14”

(1.069)

16”

(1.396)

CFM @ 1” Velocity Pressure

(Air Flow Probe “K” Factor)

448 904

1436

1891

3015 3839

Velocity Through VAV/Zone Damper

FPM

Airflow Through VAV/Zone Damper - CFM

(

P

S

inches W.C. w/ Damper Full Open)

500

98

(< 0.01)

175

(< 0.01)

273

(< 0.01)

393

(< 0.01)

535

(< 0.01)

698

(< 0.01)

750

147

(0.01)

262

(0.01)

409

(0.01)

589

(< 0.01)

802

(< 0.01)

1047

(< 0.01)

1000

196

(0.015)

349

(0.015)

545

(0.01)

785

(< 0.01)

1069

(< 0.01)

1396

(< 0.01)

1250

245

(0.025)

436

(0.02)

681

(0.015)

981

(0.015)

1336

(0.015)

1745

(0.015)

1500

294

(0.035)

523

(0.035)

818

(0.022)

1178

(0.020)

1604

0.020)

2094

(0.020)

1750

343

(0.045)

611

(0.035)

954

(0.034)

1374

(0.030)

1871

(0.030)

2443

(0.025)

2000

392

(0.065)

698

(0.043)

1090

(0.040)

1570

(0.040)

2138

(0.040)

2792

(0.030)

WattMaster reserves the right to change specifications without notice

Using the maximum acceptable velocity for a branch duct
(typically 1000-1500 FPM for minimal noise), find the smallest
Zone Damper that will deliver the required CFM as determined
by the load program. Locate the branch velocity used in the
duct design program in the left hand column of the Zone
Damper Selection Data table. Move across the table and find
the Zone Damper, which will provide the acceptable CFM to
meet the zone airflow requirements.

Note:

Compare the Zone Damper size selected against

the duct size to determine if the next size up or

down will provide acceptable performance without

requiring a transition fitting.

Pressure Independent Zone Dampers may not be slaved
together with Slaved-Zone Damper Assemblies. If more than
one damper is required for a zone, all dampers must be
selected as pressure dependent. See the Pressure Dependent
Zone Damper submittal sheet and Slaved-Zone Damper
submittal sheets for selection of master/slave damper
configurations.

OE521-XX-M Round P.I.

Zone Damper

Assembly W/ Modular Connectors

Advertising