Orion-oe736-rectzonekit-sub-01b – Orion System OE742-XX-VAVZ User Manual

Page 26

Advertising
background image


Form: Orion--OE736-02-Rect-PDZoneDmpr-Sub-01C.doc

Page

1 of 1

Description

The OE736-02-VAVZ P.D. Rectangular Damper
Kit provides a new solution for rectangular zone
damper applications. The Rectangular Damper
Kit is used in conjunction with rectangular
dampers for applications where rectangular
dampers are specified or required because of
space limitations or job requirements. The
rectangular dampers may be purchased from
WattMaster or you may get them from the
supplier of your choice. For proper control,
WattMaster recommends the use of low leakage
opposed blade dampers. The maximum
allowable damper face area for the Rectangular
Damper Kit is 6 sq. ft. The Rectangular Damper
Kit comes packaged with the OE742-32-VAVZ
VAV/Zone Controller Actuator Package and a

BK000080-00

stand-off mounting bracket. Each kit

is supplied with mounting hardware and
installation instructions.

Mounting

Before mounting the Rectangular Damper Kit,
the rectangular damper should be mounted in
the ductwork according to standard duct
installation practices. The damper should be
mounted so the damper shaft turns in a
clockwise direction to open the damper. The
Rectangular Damper Kit is simply slid over the
damper shaft, the actuator shaft collar setscrews
tightened and the supplied self-tapping screws
are used to mount the stand-off mounting
bracket to the ductwork. The standoff mounting
bracket connects to the VAV/Zone Controller
Actuator Package by securing it with the supplied
screw through its anti-rotation bushing. Detailed
mounting and installation instructions are
provided with each kit. An optional plastic conduit cover (EE000101)is available for applications requiring conduit.

OE736-02

P.D. Rectangular Damper Kit

Technical Data

OE736-02 P.D. Rectangular Damper Kit

VAV/Zone Controller Actuator Package:

Outputs:

Supply Power

24 VAC

(1) RJ-45 Cable Connection For Auxiliary Relay Board

Power Consumption

6 VA Maximum

(1) RJ-45 Cable Connection To Damper Actuator

Operating
Temperature

10

F to 149F

Uses Same 3 Conductor Terminal Block as Comm Input

Operating Humidity

90% RH Non-Condensing

Features:

Communications

RS-485 – 9600 Baud

Programming Port

Mini-DIN Jr. Port

Enclosure
Material

Fire Rated ABS Plastic

Inputs:

Zone Controller

Factory Mounted Inside The Enclosure

(1) RJ-45 Cable Connection For Digital Temperature Or
Analog Temperature

Zone Actuator

Factory Mounted To The Enclosure

Actuator Rating

45 in/lbs (6 ft

2

Damper Area Max.)

(2) Auxiliary Terminals For Duct Temperature Sensor

Labeling

Right Hand & Left Hand

(1) Terminal Block Connector For Power In

Mounting Standoff

Galvanized Steel

(1) Terminal Block Connector For Comm In

Conduit Conn.

Available Option

WattMaster reserves the right to change specifications without notice.

Three Year Warranty