Installation & Wiring

Stand-Alone Wiring

To operate the One Condenser Head Pressure Module as Stand Alone,
connect the Module to a 24 VAC power connection with an appropriate
VA rating. Up to two One Condenser Head Pressure Modules can be
connected to one HVAC unit. See Figure 5 for wiring.

Check all wiring leads at the terminal block for tightness. Be sure that
wire strands do not stick out and touch adjacent terminals. Confi rm that
all transducers required for your system are mounted in the appropriate
location and wired into the correct terminals.

Condenser Type Selection

As shown in Figure 5, set address dipswitch 1 to ON for water cooled
or to OFF for air cooled. Refer to pages 11-12 for further instructions.

Figure 5: One Condenser Head Pressure Module as Stand-Alone

SIG

GND

+V

BK

RD
WH

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All boards
must be wired with GND-to-GND
and 24 VAC-to-24 VAC. Failure
to observe polarity could result in
damage to the boards.

OE370-23-HP1C

One Condenser Head Pressure Module

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

R1

R2

GND

RELAYS

SIG 3

+5V

GND

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

OPTIONS Dipswitch

is Used for Setting

the Head Pressure

Setpoint if Not Using

Default Setpoint.

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

PWR

Condenser Fan

ECM Motor

COM

Condenser

Signal

+

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTIONS

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

- 1 AMP MAXIMUM LOAD

COMM

CONDENSER ON/OFF (Y1 CALL)

REV. VALVE ENABLE (O CALL)

COM

ADDRESS

BIN 1

BIN 2

BIN 3

COM

Set ADDRESS Dip

Switch 1 to ON for

Water Cooled or to

OFF for Air Cooled.

Currently showing

OFF for Air Cooled.

Set ADDRESS Dip
Switch 4 to OFF to

make reversing valve

"ON to Heat / OFF to

Cool”

Set to ON to make

reversing valve “ON

to Cool / OFF to Heat.

Currently showing

OFF.

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102057-A

Rev.: 1J

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VA

C

GND

HEAD
PRESSURE
TRANSDUCER #1/

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

PWM2+

One Condenser Head Pressure Module

1C

Orion No.:OE370-23-HP

AAON No.:

R74860

AO1

AO2

GND

COND. SIGNAL

NOT USED

PWM1-

PWM1+

PWM2-

COND. FAN

NOT USED

COND. FAN

NOT USED

GND

RELA

Y

CONT

ACT

RA

TING IS 1

AMP

MAX @ 24 V

AC

COND. ENABLE

NOT USED

NOT USED

R1

R2

R3

R4

RC

RELAY COMMON

BIN 1

BIN 2

BIN 3

COM

NOT USED

COMMON

COND. ENABLE INPUT
REV. VLV. INPUT ENABLE

A1

A2

A3

A4

REV. VLV. ENABLE

www.aaon.com

R2

REVERSING VALVE A ENABLE

+24 Volts

Duty Cycle

YELLOW
BLUE +24 OUT

Advertising