One condenser head pressure module, Sequence of operation – Orion System One Condenser Head Pressure Module User Manual

Page 14

Advertising
background image

One Condenser Head Pressure Module

Technical Guide

14

Sequence of Operation

ADDRESS Dip Switch 4 Settings

Switch Description

OFF

Reversing Valve On to Heat / Off to Cool

ON

Reversing Valve On to Cool / Off to Heat

Table 5: ADDRESS Dip Switch 4 Settings for Reversing Valve

ADDRESS Dip Switch 2 Settings

Switch Description

OFF

Set to OFF if Using only (1) Head Pressure Module
or if this is Module 1 when Using (2) Head Pressure
Modules.

ON

Set to ON if this is Module 2 when Using (2) Head
Pressure Modules.

Table 4: ADDRESS Dip Switch Address Settings When Connected to VCM-X