One Condenser Head Pressure Module
Technical Guide
14
Sequence of Operation
ADDRESS Dip Switch 4 Settings
Switch Description
OFF
Reversing Valve On to Heat / Off to Cool
ON
Reversing Valve On to Cool / Off to Heat
Table 5: ADDRESS Dip Switch 4 Settings for Reversing Valve
ADDRESS Dip Switch 2 Settings
Switch Description
OFF
Set to OFF if Using only (1) Head Pressure Module
or if this is Module 1 when Using (2) Head Pressure
Modules.
ON
Set to ON if this is Module 2 when Using (2) Head
Pressure Modules.
Table 4: ADDRESS Dip Switch Address Settings When Connected to VCM-X