One condenser head pressure module, Troubleshooting, Technical guide – Orion System One Condenser Head Pressure Module User Manual

Page 17: Pressure transducer troubleshooting

Advertising
background image

Technical Guide

One Condenser Head Pressure Module

17

Troubleshooting

Table 6: One Condenser Head Pressure Module
Transducer Chart

Pressure Transducer Troubleshooting

If you suspect there is a problem with the Module related to pressure
transducer measurements, reference Table 6 below.

Pressure Sensor Chart

Voltage Pressure Voltage Pressure

0.5

0

2.6

350

0.6

17

2.7

367

0.7

33

2.8

384

0.8 50

2.9

400

0.9 67

3.0

417

1.0 83

3.1

434

1.1

100

3.2

450

1.2

117

3.3

467

1.3

133

3.4

484

1.4

150

3.5

500

1.5

167

3.6

517

1.6

183

3.7

534

1.7

200

3.8

550

1.8

217

3.9

567

1.9

233

4.0

584

2.0

250

4.1

600

2.1

267

4.2

617

2.2

283

4.3

634

2.3

300

4.4

650

2.4

317

4.5

667

2.5

334

Advertising