Troubleshooting
Table 6: One Condenser Head Pressure Module
Transducer Chart
Pressure Transducer Troubleshooting
If you suspect there is a problem with the Module related to pressure
transducer measurements, reference Table 6 below.
Pressure Sensor Chart
Voltage Pressure Voltage Pressure
0.5
0
2.6
350
0.6
17
2.7
367
0.7
33
2.8
384
0.8 50
2.9
400
0.9 67
3.0
417
1.0 83
3.1
434
1.1
100
3.2
450
1.2
117
3.3
467
1.3
133
3.4
484
1.4
150
3.5
500
1.5
167
3.6
517
1.6
183
3.7
534
1.7
200
3.8
550
1.8
217
3.9
567
1.9
233
4.0
584
2.0
250
4.1
600
2.1
267
4.2
617
2.2
283
4.3
634
2.3
300
4.4
650
2.4
317
4.5
667
2.5
334
Advertising