Appendix for Version 1.06 and Earlier

Version 1.06 and Earlier

Version 1.06 and earlier have several differences from version 1.07 and
later. Please refer to the Dipswitches in Figures 8 & 9 and the Tables
9 & 10
for detailed information.

Figure 8: Version 1.06 and Earlier One Condenser Head Pressure Module Wiring Diagram
(VCM-X Connection)

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

COM

Condenser Fan

ECM Motor

+

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP1C-A

One Condenser Head Pressure Module

Connect To E-BUS

Distribution Module

or VCM-X E-BUS

Controller

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

BIN 2

R1

R2

GND

RELAYS

ADDRESS

SIG 3

+5V

GND

BIN 1

COM

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

COM

Condenser

Signal

+

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!!
Observe Polarity! All boards must be
wired with GND-to-GND and 24 VAC-to-
24 VAC. Failure to observe polarity could
result In damage to the boards.

HSSC Cable

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY

ALL RELAY OUTPUTS

ARE

- 1 AMP MAXIMUM LOAD

COMM

OPTIONS Dip Switch

Setting Not Required

When Connected To

VCM-X Modular or

VCM-X WSHP

Controller

Set ADDRESS Dip

Switch 1 to ON for

Water Cooled or to

OFF for Air Cooled.

Currently showing OFF

for Air Cooled.

ADDRESS Dip Switch

4 should always be set

to OFF to make

reversing valve "ON to

Heat / OFF to Cool”

Currently showing OFF.

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102057-A

Rev.: 1F

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VA

C

GND

BIN 1

BIN 2

COM

HEAD
PRESSURE
TRANSDUCER #1

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

COMMON

PWM2+

One Condenser Head Pressure Module

1C

Orion No.:OE370-23-HP

AAON No.:

R74860

AO1

AO2

GND

COND. ENABLE

HEAT ENABLE

COND. SIGNAL

NOT USED

PWM1-

PWM1+

PWM2-

COND. FAN

NOT USED

COND. FAN

NOT USED

GND

www.aaon.com

RELA

Y

CONT

ACT

RA

TING IS 1

AMP

MAX @ 24 V

AC

COND. ENABLE

HEAT ENABLE

NOT USED

NOT USED

R1

R2

R3

R4

RC

RELAY COMMON

VCM-X Connection

Version 1.06 and earlier do not utilize Dipswitch 2 when the module is
connected to a VCM-X Series Controller.