One condenser head pressure module, Installation & wiring, Technical guide 6 – Orion System One Condenser Head Pressure Module User Manual

Page 6

Advertising
background image

One Condenser Head Pressure Module

Technical Guide

6

Installation & Wiring

VCM-X Modular or VCM-X WSHP

to One Condenser Head Pressure

Module Wiring

The One Condenser Head Pressure Module connects to the E-BUS
Distribution Module using a modular HSSC cable. The One Condenser
Head Pressure Module requires a 24 VAC power connection with an
appropriate VA rating.

The E-BUS Distribution Module connects to the VCM-X Modular
Controller, VCM-X WSHP Controller, VCM-X Expansion Module, or
12 Relay Expansion Module using the I

2

C port. See Figure 3 below for

wiring. Up to (2) One Condenser Head Pressure Modules can be used
per E-BUS Controller.

Any E-BUS Module can be connected to each of the four E-BUS

Dis-

tribution Module’s output ports or can be daisy-chained together using
HSSC cables.

Figure 3: VCM-X WSHP Controller to One Condenser Head Pressure Module Wiring Diagram

Connect To

E-BUS

Distribution

Module

Line Voltage

24 VAC

GND

Line Voltage

All Comm Loop Wiring Is

Straight Thru

24VAC

GND

Local Loop

RS-485

9600 Baud

See Individual Component

Wiring Diagrams For

Detailed Wiring Of Analog

Inputs And Outputs

For Stand Alone Applications,
Connect To System Manager.

For Network Applications

Connect To Next Controller

And/Or MiniLink PD On Local Loop.

G - Fan ON/OFF Only

R - 24VAC

Relay Output Contacts
R2 Thru R5 May Be User-
Configured For The Following:
1 - Heating Stages
2 - See Note 1 Below
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat
Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper
12 - Heat Wheel

Note: 1.) When Using the HP1C Module,
All Compressors Will Be Wired From the
Protection Module, Not the VCM-X
Controller.
2.) A Total Of 20 Relays Are Available By
Adding Relay Expansion Modules. All
Expansion Module Relay Outputs Are User
Configurable As Listed Above.

Connect FRP Tubing To High Pressure
Port (Bottom Tube) and Route To Static
Pressure Pickup Probe Located In Unit
Discharge. Leave Port Marked “Lo” Open
To Atmosphere

OE271

Static Pressure

Transducer

Splice If Required

Connect To E-BUS Distribution Module or
Expansion Module(s)
(When Used)

Connect To Digital Room Sensor And/Or
Digital CO Sensor

2

Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

T to T, R to R & SHLD to SHLD

Size Transformer For
Correct Total Load.
VCM-X Controller = 8 VA

Note:
All Relay Outputs Are Normally
Open And Rated For 24 VAC Power
Only. 1 Amp Maximum Load.

AI1

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

AI2

AI3

AI4

AI5

AI7

AI1 SET

AI2 SET

AI3 SET

AI4 SET

AI5 SET

AI7 SET

Jumpers

OE332-VCMX-WSHP

VCM-X WSHP Controller