Technical Guide

One Condenser Head Pressure Module

3

Overview

NOTE: Software version 1.06 and earlier contain a few

differences from version 1.07 and later. For version
1.06 and earlier details, please see the Appendix.
The version number can be found on the upper right
of your module.

The One Condenser Head Pressure Module (OE370-23-HP1C) monitors
four individual head pressure transducers and controls the Condenser
Fan or Water Valve based on the highest of the four readings. If this is
a heat pump unit, the module is able to detect when the unit is in Heat
Pump Heating mode and will force the condenser signal to 100% until
it leaves this mode.

The One Condenser Head Pressure Module is designed to work stand-
alone by using its OPTIONS Dip Switch to adjust the Head Pressure
setpoint.

Up to (2) One Condenser Head Pressure Modules can be daisy-chained
together and connected to the VCM-X Modular Controller or VCM-X
WSHP Controller using the E-BUS Distribution Module allowing the
One Condenser Head Pressure Module to receive setpoints from the
Controller. Up to (2) modules can also be daisy-chained together and
directly connected to the VCM-X Modular E-BUS or VCM-X WSHP
E-BUS Controller. See chart on page 2 for part numbers.

The One Condenser Head Pressure Module also provides a pulse width
modulation (PWM) signal or voltage output signal to control the con-
denser fan.

The One Condenser Head Pressure Module requires a 24 VAC power
connection with an appropriate VA rating.

Module Overview

Figure 1: One Condenser Head Pressure Module

Features

The One Condenser Head Pressure Module provides the following:



Can be operated stand alone or (2) can be daisy-chained

together and connected to a VCM-X Modular or VCM-X

WSHP Controller using the E-BUS

Distribution Module to

E-BUS

interface

Two modules can be daisy-chained together and be directly

connected to a VCM-X Modular E-BUS or VCM-X WSHP

E-BUS

Controller



Monitors up to four individual head pressure transducers



Provides control of Condenser Output Signal based on the

highest reading of head pressure transducers



Capable of monitoring a Reverse Valve Signal



Forces Condenser Fan to 100% while in the Heat Pump

Heating

Mode

NOTE: The One Condenser Head Pressure Module contains

no user-serviceable parts. Contact qualifi ed technical
personnel if your Module is not operating correctly.

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102057-A

Rev.: 1J

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VA

C

GND

HEAD
PRESSURE
TRANSDUCER #1/

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

PWM2+

One Condenser Head Pressure Module

1C

Orion No.:OE370-23-HP

AAON No.:

R74860

AO1

AO2

GND

COND. SIGNAL

NOT USED

PWM1-

PWM1+

PWM2-

COND. FAN

NOT USED

COND. FAN

NOT USED

GND

RELA

Y

CONT

ACT

RA

TING IS 1

AMP

MAX @ 24 V

AC

COND. ENABLE

NOT USED

NOT USED

R1

R2

R3

R4

RC

RELAY COMMON

BIN 1

BIN 2

BIN 3

COM

NOT USED

COMMON

COND. ENABLE INPUT

REV. VLV. INPUT ENABLE

A1

A2

A3

A4

REV. VLV. ENABLE

www.aaon.com

ALARM

ANALOG

STAT

COMM

R1

R2

GND

RELAYS

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

ADDRESS

OPTIONS

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+5V

SIG 1

GND

BIN 1

BIN 2

BIN 3

COM

Advertising