One Condenser Head Pressure Module

Technical Guide

8

E-BUS Controller to One Condenser Head Pressure Module Wiring

VCM-X Modular E-BUS or VCM-X WSHP

E-BUS Controller to One Condenser

Head Pressure Module Wiring

Up to (2) One Condenser Head Pressure Modules can be daisy-chained
together and connected to the E-BUS Controller using a modular HSSC
cable. The One Condenser Head Pressure Module requires a 24 VAC
power connection with an appropriate VA rating. See Figure 4 below
for wiring.

Any E-BUS Module can be connected to the E-BUS Controller’s E-BUS
port or can be daisy-chained together using HSSC cables.

NOTE: Contact Factory for the correct HSSC cable length for

your application. Cables are available in ¼, ½, 1, 2, 3,
4, and 5 Meter lengths and 100 and 150 Foot lengths.

Figure 4: VCM-X E-BUS Controller to Two Condenser Head Pressure Module Wiring Diagram

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

SIG

GND

+V

BK

RD
WH

Head Pressure Transducers

0 - 667 PSI

(One Per Refrigerant Circuit)

OE370-23-HP1C

One Condenser Head Pressure Module

OPTIONS Dip Switch Setting Not

Required When Connected To

VCM-X Modular E-BUS or VCM-X

WSHP E-BUS Controller

+5V

SIG 2

GND

OP

T

IO

N

S

ALARM

ANALOG

STAT

+5V

COMM

GND

SIG 4

GND

R1

R2

GND

RELAYS

SIG 3

+5V

GND

+5V

SIG 1

R3

R4

Rc

AO1

AO2

PWM1-

PWM1+

PWM2-

PWM2+

PWR

COM

+

Condenser

Signal A

Connect To Other

WattMaster-Approved

E-BUS Expansion Module(s)

HSSC Cable

24 VAC Transformer

3 VA Minimum

Line Voltage

24 V

A

C

GND

WARNING!! Observe
Polarity! All boards must be
wired with GND-to-GND and
24 VAC-to-24 VAC. Failure to
observe polarity could result in
damage to the boards.

CONDENSER A ENABLE

R1

HVAC UNIT CONNECTION

NOTE:

NORMALLY OPEN AND

RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

ALL RELAY OUTPUTS

ARE

COMM

HSSC Cable

Connect To VCM-X E-BUS

Controller or VCM-X WSHP E-BUS Controller

Set ADDRESS Dip Switch 1

to ON for Water Cooled or to

OFF for Air Cooled. Currently

showing OFF for Air Cooled.

Set ADDRESS Dip Switch 2

to OFF on all communicating

applications unless it is

intended to be the Second

Head Pressure Module on a

system. If set to ON, it will

not communicate. Currently

showing OFF.

Set ADDRESS Dip Switch 4

to OFF to make reversing

valve "ON to Heat / OFF to

Cool” Set to ON to make

reversing valve “ON to Cool /

OFF to Heat. Currently

showing OFF.

ADDRESS

BIN 1

BIN 2

BIN 3

COM

LED BLINK CODES

LED NAME

STAT

BLINKS QTY. OF SENSORS INSTALLED

LED NAME

ALARM

NO PROBLEMS

0

NO SENSORS DETECTED

1

HIGH HEAD PRESSURE DETECTED

2

LOW HEAD PRESSURE DETECTED

3

WattMaster Label

#LB102057-A

Rev.: 1J

E-BUS

Connector

E-BUS

Connector

+5V

SIG 1

GND

+5V

SIG 2

GND

+5V

SIG 3

GND

+5V

SIG 4

GND

+24

VA

C

GND

HEAD
PRESSURE
TRANSDUCER #1/

HEAD
PRESSURE
TRANSDUCER #2

HEAD
PRESSURE
TRANSDUCER #3

HEAD
PRESSURE
TRANSDUCER #4

PWM2+

One Condenser Head Pressure Module

1C

Orion No.:OE370-23-HP

AAON No.:

R74860

AO1

AO2

GND

COND. SIGNAL

NOT USED

PWM1-

PWM1+

PWM2-

COND. FAN

NOT USED

COND. FAN

NOT USED

GND

RELA

Y

CONT

ACT

RA

TING IS 1

AMP

MAX @ 24 V

AC

COND. ENABLE

NOT USED

NOT USED

R1

R2

R3

R4

RC

RELAY COMMON

BIN 1

BIN 2

BIN 3

COM

NOT USED
COMMON

COND. ENABLE INPUT
REV. VLV. INPUT ENABLE

A1

A2

A3

A4

REV. VLV. ENABLE

www.aaon.com

R2

REVERSING VALVE A ENABLE

+24 Volts

Duty Cycle

YELLOW

BLUE +24 OUT

Condenser Fan

ECM Motor