One Condenser Head Pressure Module

Technical Guide

22

Appendix for Version 1.06 and Earlier

Table 9: OPTIONS Dip Switch/Head Pressure Setpoint Settings for Stand-Alone Operation

OPTIONS Dip

Switch Settings

Head Pressure Setpoint

Air Cooled Condenser

Water Cooled Condenser

Binary Value

R410-A

R22

R410-A

R22

0

340 (DEFAULT)

200 (DEFAULT)

235 (DEFAULT)

145 (DEFAULT)

1

260

160

210

110

2

270

170

220

120

3

280

180

230

130

4

290

190

240

140

5

300

200

250

150

6

310

210

260

160

7

320

220

270

170

8

330

230

280

180

9

340

240

290

190

10

350

250

300

200

11

360

260

310

210

12

370

270

320

220

13

380

280

330

230

14

390

290

340

240

15

400

300

350

250

NOTE: R22 refrigerant can only be used with the One Condenser Head Pressure Module versions 1.03 to 1.06.
You must cycle power after setting Dip Switch values.