Fault

Possible cause

Check

Remedial measures

The unit is running
with reduced or
without cooling or
heating output

Filter is dirty / air inlet / outlet
opening is blocked by by debris

Have the filters been cleaned?

Clean the filters

Doors and windows open /
heating or cooling load was
increased

Have there been any
constructional /
application-related changes?

Close doors and windows /
install additional systems

Neither cooling nor heating
mode has been set

Does the "cooling / heating"
symbol appear in the display?

Correct the settings for the unit

Fins of outdoor component are
blocked by debris

Is the fan on the outdoor
component running are the fins
unobstructed?

Check fan or winter regulation,
reduce air resistance

Leaking refrigerant circuit

Are there signs of frost on the
fins of the indoor unit?

Repair by a specialist

Condensation output
on the unit

Drain pipe of the collection
container blocked / damaged

Is unobstructed condensation
drainage ensured?

Clean the drainage pipe and
collection container

Faulty external condensation
pump or float

Is the condensation pan full
of water and the pump is not
working?

Call out a specialist to replace
the pump

Condensation has not drained
away and has collected in the
condensation pipe

Is the condensation pipe routing
sloped downhill and is it clear?

Route the condensation pipe
in a downhill slope or clean it if
necessary

Condensation does not drain off

Are the condensation pipes
unblocked and is there a steady fall?
Are the condensation pump and
float switch functioning correctly?

The condensation pipe must have
a fall. If necessary, clean the pipe.
A faulty condensation pump and
float switch should be replaced.

Problem display by blinker code

Display

Cause

Required action

E1

Sensor air circulation faulty / tripped

Contact specialist dealer

E2

Sensor on vaporiser faulty / tripped

Contact specialist dealer

E4

Cooling mode: No cooling output after 30 minutes

Heating mode: No heat output after 30 minutes

Contact specialist dealer

E5

Cooling mode: Antifreeze protection has responded

Heating mode: Overheating protection has tripped

Contact specialist dealer

E6

Bridge inner control line interrupted

Check bridge plug

Leaking refrigerant circuit

Are there signs of severe frost
on the large stop valve?

Repair by a specialist.

Icing up of unit

In conjunction with RXM:
Heating/automatic mode set

Check mode setting

Set cooling mode