Technical data – REMKO RXW 261 User Manual

Page 23

Advertising
background image

23

Series

RXW 261

RXW 351

RXW 521

RXW 681

Operating mode

Wall unit for cooling and heating

Nominal cooling output

1)

kW

2,69

3,59

5,27

6,84

Nominal heating output

2)

kW

2,96

4,24

6,31

7,72

Energy efficiency class, cooling

1)

A

A

B

B

Energy efficiency ratio EER

1)

3,32

3,23

3,12

3,05

Energy efficiency class, heating

2)

A

A

C

C

Coefficient of performance COP

2)

3,70

3,66

3,29

3,24

Operating range (room volume), approx.

80

110

160

230

Adjustment rangeroom temperature

°C

+16 to +31

Working range

°C

+15 to +31

Refrigerant

R 410A

4)

Operating pressure max. / per cooling circuit

kPa

4200 / 4200

Air flow rate per stage

m³/h

320/370/420

380/450/520

600/700/800

800/900/1000

Noise output per stage

3)

dB(A)

30/34/38

32/36/40

35/39/43

36/40/45

Voltage supply

V/Hz

230 / 1~ / 50

Protection degree

IP

X0

Nom. electrical power consumption, cooling

1)

kW

0,03

0,04

0,04

0,05

Nom. electrical power consumption, heating

2)

kW

0,03

0,04

0,04

0,05

Electr. nominal power consumption cooling

1)

A

0,15

0,19

0,23

0,30

Electr. nominal power consumption heating

2)

A

0,15

0,19

0,23

0,30

Refrigerant connection, injection pipe

Inches (mm)

1/4 (6,35)

3/8 (9,52)

Refrigerant connection, suction pipe

Inches (mm)

3/8 (9,52)

1/2 (12,70)

5/8 (15,90)

Condensation connection

mm

17

17

17

17

Dimensions Height

mm

275

275

275

320

Width

mm

790

790

930

1035

Depth

mm

200

200

200

220

Weight

kg

8,0

10,0

12,0

16,0

Serial number

820...

821...

822...

823...

Computerised part no.

1619120

1619130

1619140

1619150

Technical data

1) Air intake temp. TK 27°C / FK 19°C, outdoor temp. TK 35°C / FK 24°C, max. air volume, 5m pipe length in combination with RXS 261H - 681H
2) Air intake temperature TK 20°C outdoor temperature TK 7°C, FK 6°C, max. air volume, 5m pipe length in combination with RXS 261H-1200H
3) Distance 1 m free air

4) Contains greenhouse gas according to Kyoto protocol

Advertising