Wire the protocol converter, 1 power supply & ground connections, Power supply & ground connections – RLE Protocol Converter V.2.4 User Manual

Page 16: Figure 2.2, 24vdc power supply connection

Advertising
background image

16

Protocol Converter User Guide

800.518.1519

2

Installation

2.3.

Wire the Protocol Converter

If you plan to use the EIA-485 port for Modbus RTU communication, RLE Technologies

recommends an 18 AWG shielded, twisted-pair stranded copper wire for the connection. RLE

recommends no more than 2,000 feet (609.6m) of wire at this specification. If longer runs are

needed, contact RLE Technologies for application guidance.

2.3.1 Power Supply & Ground Connections

To provide power and ground connections to the Protocol Converter:

1

Connect an 18 AWG ground wire from the ground terminal to a suitable earth ground.

2

Connect power to the Protocol Converter in one of two ways, as shown in

Figure 2.2

:

a

Plug the wall adapter (provided) into the power jack on the Protocol Converter and into a

UPS outlet.

b

Connect a dedicated 24VDC power supply to the + and - terminals to the left of the

power jack.

IMPORTANT

RLE Technologies recommends powering the Protocol Converter from a UPS (uninterruptible

power supply) so the Protocol Converter can send alarm notifications during a power outage.

Figure 2.2

24VDC Power Supply Connection