RLE Protocol Converter V.2.4 User Manual

Page 47

Advertising
background image

rletech.com

Protocol Converter User Guide

47

3

Configuration

Max. EIA-485 Device

Response Time

This setting determines the allowable response time, in

seconds, from devices before the Protocol Converter times out.
Set a value in the range of 0.3 to 9.9 seconds. If the Protocol

Converter times out, an offline alarm will be triggered and the

device’s status color will change on the Protocol Converter’s

home page.

SNMP/BACnet/IP Device

Poll Rate

Determines the rate, in packets per second, at which data is

sent. The drop-down provides selections of 1, 5, or 10.

Modbus/TCP Open

Requests

Define the number of retries the Protocol Converter should

execute.

Device Write Enable

Determines whether or not client write operations to the

Protocol Converter are translated, written to the specific server

device or register and then read back by the Protocol Converter

to update the local register data.
The write operations are generated via SNMP Sets, BACnet

Write-Property and Modbus Preset Single Register commands.
Select Yes to enable the Protocol Converter to perform write

operations. Default: Yes.

EIA-485 Port (1, 2, 3)

Function

The port type for the EIA-485 port. Choose Modbus Slave or

Modbus Master.

EIA-485 Port (1, 2, 3)

Baud Rate

Speed of the EIA-485 port. Choose 1200, 2400, 9600 (default),

or 19200. Ports 2 and 3 can also run at 38400 baud.

EIA-485 Port (1, 2, 3)

Parity

Select None (default), Even, or Odd for the Parity output.

EIA-485 Port (1, 2, 3) Stop

Bits

Select 1 or 2.

EIA-485 Slave Address

An RTU address in the range 1 to 254. To disable transmission

on the EIA-485 port, leave the value at 0.

BACnet MS/TP Port 3

Max Master

Number of BACnet masters allowed on the MS/TP network.

Option

Description

Table 3.8

EIA-485/Modbus/BACnet-MSTP Ports Configuration Options