Configuration

Figure 3.28

BACnet PICS Information

UDP Port

This is the user datagram protocol port, which is used by

applications to send messages to a device (in this case, the

Protocol Converter).

Enter 0 to specify port 47808 as the UDP port. If another

port is specified by your application, enter a new port

number in this field.

Default setting: 0 (47808)

BACnet-MS/TP Port3 Max

Master

Set the slave address, 1/127. 0 = slave only.

Default setting: 0

BACnet/IP Read-Multiple

Enable or disable this feature.

BACnet PICS link

This link displays the protocol implementation conformance

statement (PICS). The PICS Web page shows general

BACnet capabilities of the device (for example, available

LAN options). An example of a BACnet PICS page is

shown in

Figure 3.28

.

Engineering Units

Click this link to view a list of the units supported by the

device, coupled with their numerical BACnet identifiers.

BACnet/IP COV Clients

This is a list of the BACnet clients that will receive a

notification when the Protocol Converter notes a change of

value (COV).
Configure these addresses on the Registers tab.

BACnet BBMD-BDT

This feature is used by some BACnet masters for discovery

on different subnets. Enter information as applicable to

your application.

Option

Description

Table 3.9

BACnet Server Configuration Options (continued)