5 bacnet register configuration, Bacnet register configuration, Figure 3.21 bacnet register configuration – RLE Protocol Converter V.2.4 User Manual

Page 42: Table 3.7, Bacnet register configuration options

Advertising
background image

42

Protocol Converter User Guide

800.518.1519

3

Configuration

3.6.5 BACnet Register Configuration

If you are configuring a BACnet device, the register configuration page looks like this:

Figure 3.21

BACnet Register Configuration

1

Type an appropriate value in each field, or choose the value from the drop-down.

Option

Description

BACnet Instance

The Instance number used by the Protocol Converter to

poll the desired data from that BACnet device.

Instance Type

Select the type of BACnet instance from the drop-down

menu. Choose Analog Input (AI), Analog Output (AO),

Analog Value (AV), Binary Input (BI), Binary Output (BO),

Binary Value (BV), Multistate Input (MI), Multistate Output

(MO), or Multistate Value (MSV).

Gain

The gain value of the raw data being received if needed.

Calculate as follows: (Sensor High Range Value - Sensor

Low Range Value) / 4

Offset

The offset value of the calculated reading to the register.

Calculate as follows: Sensor Low Range Value - Gain

Label

Designate a name (label) for the register being configured.

Labels can contain up to 30 alphanumeric characters.

Table 3.7

BACnet Register Configuration Options