Figure 3.14 register configuration navigation – RLE Protocol Converter V.2.4 User Manual
Page 37

rletech.com
Protocol Converter User Guide
37
3
Configuration
2
Click Submit Changes located in the upper left hand corner of the web page.
3
Once the changes have been accepted, click the Next>> link in the bottom navigation bar to
configure the next register.
You can also click the First, <<Prev, Last, or End links to go to those locations in the list of
registers.
Figure 3.14
Register Configuration Navigation
BACnet Instance
The number used by a BACnet master for polling data from
the Protocol Converter.
Possible values include Analog Instance (AI) or Binary
Instance (BI).
BACnet Engineering Units
In the BACnet ASHRAE standard, numbers correlate with
units of measure. Refer to the BACnet ASHRAE standard
for more information.
BACnet COV Client
(COV - Change of Value)
The IP address of the BACnet master that is polling the
FDS-PC.
BACnet COV SPID
Enter the Subscriber Process Identifier.
You’ll also need to designate if it should be Confirmed or
Unconfirmed.
Confirmed: When a change of value is sent to the device, it
will look for an acknowledgement of the change to be sent
in response. If no acknowledgement is received, the
change will be sent again. This cycle will repeat until an
acknowledgement is received.
Unconfirmed: A change of value is sent, and the device
doesn’t look for an acknowledgement.
Select the Confirmed or Unconfirmed radio button to
indicate your preference.
BACnet COV Increment
Amount that the present value of a point needs to change
before the change of value message is initiated to the
BACnet master.
BACnet COV Period
Interval, in seconds, between polling operations.
SNMP register/Table OIDs
The OID (object identifier) being polled from the SNMP
software. The Protocol Converter displays the OIDs used
for Integer data, Float data, and the Label assigned.
SNMP Modbus Device
Register/Table OIDs
Formatted to
BASE.DEVICENUMBER.REGISTERNUMBER where
BASE is the OID for this table, DEVICENUMBER is the
device’s number in the Protocol Converter (1-32) and the
REGISTERNUMBER reflects the appropriate device point
address.
Option
Description
Table 3.5
Modbus Register Configuration Page Options