Varmeca - 20, Variable speed motor or geared motor, 3 - connections – Watson-Marlow Varmeca User Manual

Page 27: 3 - adjusting the mini dip switches, 1 - wiring precautions, 2 - terminal blocks, Leroy-somer

Advertising
background image

25

INSTALLATION AND MAINTENANCE

VARMECA - 20

Variable speed motor or geared motor

CONNECTIONS

LEROY-SOMER

Réf. 3481 - 4.33/c - 09.01

2.3 - Adjusting the MINI DIP switches

These switches are used to select the reference, the U/F ratio and the reference on the analogue input of terminal 2 (see
VARMECA - 20 parameter-setting manual).

Factory settings

CAUTION:
These operations should only be performed in exceptional circumstances and must be carried out by experienced and
qualified personnel.

MINI DIP

OFF

ON

K1

4 - 20mA

0 - 10V

Speed reference

reference

reference

K2

4 - 20mA

0 - 10V

Analogue input

terminal 2

K3

U/F ratio

U/F ratio

U/F ratio

factory setting

constant

ON

K3 K2

P2

P1

P3

K1

OFF

1

2

3

4

5

6

7

8

9

3 - CONNECTIONS

• The voltages on the power terminal blocks and
the cables connected to them may cause fatal
electric shocks. The drive stop function does not

protect against these high voltages.

• The drive contains capacitors which remain

charged at a fatal voltage even after the power supply has
been switched off.

• After switching off the drive, wait for 2 min so that

the internal circuits can discharge the capacitors, before
removing the protection (for the single-phase range).

• The drive power supply must be protected

against overloads and short-circuits.

• It is vital to respect the rating of protection

devices.

• Connection with copper conductor only.

3.1 - Wiring precautions

- When the VARMECA - 20 is controlled remotely, avoid
parallel routing of power cables and control cables.
- All remote control cables must be shielded and have a
cross-section between 0.22 mm

2

and 1 mm

2

. The shielding

should be connected to earth at both ends.
- Check that the different earth points are actually at the same
voltage.
- Incorporate a bend where the cables enter the cable glands
so that water cannot penetrate the terminal box.
- Tighten the cable glands firmly.

en

3.2 - Terminal blocks

3.2.1 - Layout

3.2.2 - P1 terminal block

Standard configuration

Marking

Functions - Characteristics

Connection of protected mains supply phases

L1, L2

200V to 240V ± 10 %, 50-60Hz in single-phase

L1, L2, L3 200V to 480V ± 10%, 50-60Hz in 3-phase

PE

Earth connection

R1, R2

Connection of the braking resistor
Min. resistance value = 180 Ohms

ON

K3 K2

P2

P1

P3

K1

OFF

1

2

3

4

5

6

7

8

9 10 11 12

L1

L2

L3

PE

R+

R-

Control/Command

Mains

M/N :

77b3000A

P/N :

VARMECA21

S/N :

20106000748

1

Locking logic input
Terminals 1 and 3 not connected: drive disabled
Terminals 1 and 3 connected: drive enabled

2

Analogue speed output 0 to +10V, 3mA
0V = zero speed
10V = maximum speed
Analogue input (see VARMECA - 20
parameter-setting manual)

3

Source +24V, 30mA (± 10%)
Common at terminal 10

4

Source +10V, 30mA (± 10%)

5

0V - Connected to the terminal block earth

6

Reference input 0 to +10V or 4-20mA
0-10V: input impedance = 100 kOhms
4-20mA: input impedance = 0.5 kOhms

7

Reverse/Stop logic input

8

Forward/Stop logic input

9

Ramp selection logic input
1s (for 0 at 50Hz) : terminals 9 and 10 not connected
3s (for 0 at 50Hz): terminals 9 and 10 connected

10

Source +24V - 30mA
Common at terminal 3

11, 12

Fault relay - volt-free contact 250V 1A
Contact open: switched off or faulty
Contact closed: in run status

Marking

Functions - Characteristics

INSTALLATION & CONNECTIONS

Advertising