4 - COMMISSIONING

• Before switching on the VARMECA - 20 motor,
check that the electrical connections are

correct, and that any moving parts are mechanically
protected.

• For the safety of personnel, the VARMECA - 20

must not be switched on with the protective cover
removed.

• The run command has been enabled, thus the

motor starts as soon as it is switched on.

4.1 - VARMECA - 20

4.1.1 - Starting with remote control

- Power-up: Terminals 1 and 3 are connected.
- Activate the run command corresponding to the required
direction. The motor starts.
- Adjust the speed reference using the chosen reference
(0/10V or 4/20mA).

4.1.2 - Starting on power-up with the speed
control knob option

- Power-up: The green indicator lamp is on continuously. As
control terminals 1 and 3 (enable) and 8 and 10 are
connected together, the motor starts running forward.
- Set the speed reference using the side control knob.

4.2 - VARMECA - 20 with remote
potentiometer option

- Power-up: Terminals 1 and 3 are connected.
- Select the required ramp.
- Set the reference using the 10 k

remote potentiometer.

- Select the required direction of rotation. The motor starts.

5 - FAULTS - DIAGNOSTICS

Information relating to the status of the VARMECA - 20 is provided by 2 indicator lamps located on the control options.

Trips can be cleared by switching off the VARMECA - 20

.

Colour and state of

indicator lamps

Reason for fault

Checks to be performed

Steady green

No fault
Mains present

If the motor does not rotate, check that:
- terminals 1 and 3 are connected
- a run command has actually been enabled: terminals 7 and 10 or 8 and 10
are connected

Flashing green and red

Current limiting

• Check that the motor is not overloaded or stalled

Flashing green

Overload

• The motor is overloaded: check the motor current using a clamp ammeter
(section 6.2.2)

Steady red

• Short-circuit of a

motor winding

• Locked motor rotor
• Faulty insulation

of a winding

• I

2

t overheating

• Internal fault

• Check that no incident has occurred
• Switch off and then on again to clear the fault
• Check that the deceleration ramp is long enough (5s) for applications with
high inertia
• If the fault remains, consult LEROY-SOMER

Flashing red

• Undervoltage
• Overvoltage

• Check the mains voltage
• Check that the deceleration ramp is long enough (5s) for applications with
high inertia
• Switch off and then on again