Westermo IDW-90 User Manual

Page 14

Advertising
background image

14

6620-2200

RS-232
Electrical specification

EIA/TIA-232

Data rate

1 200 bit/s – 115.2 kbit/s

Data format

7 or 8 data bits, Odd, even or none parity, 1 or 2 stop bits;

Σ 9 – 12 bits

Protocol

Transparent

Retiming

Yes

Transmission range

Cable length

≤15 m

Isolation to

Power port 3 kV

rms

50 Hz 1 min

ISDN line 2 kV

rms

50 Hz 1 min

I/O 1.5 kV

rms

50 Hz 1 min

Galvanic connection to

RS-485

Connection

9-pin D-sub female (DCE)

Shielded cable

Not required*

Miscellaneous

Do not connect RS-232 and RS-422/485 simultaneously

Generic I/O Input
Electrical specification

Opto isolated input

Input voltage range

0 – 60 VDC

Input current

5mA @ 60 VDC

Input inactive
Input active

U

in

<2.5 V

U

in

>5.0 V

Transmission range

Cable Length

≤ 15 m

Connection

Detachable screw terminal (DCE)

Connector size

0.2 – 2.5 mm

2

(AWG 24 – 12)

Isolation to

Power port 3 kV

rms

50 Hz 1 min

ISDN line 2 k

Vrms

50 Hz 1 min

RS-232 2 kV

rms

50 Hz 1 min

RS-485 2 kV

rms

50 Hz 1 min

I/O output 2 kV

rms

50 Hz 1 min

Shielded cable

Not required*

* To minimise the risk of interference, a shielded cable is recommended when the cable is located inside 3 m

boundary to the rails and connected to this port.

The cable shield should be properly connected (360°) to an earthing point within 1 m from this port.

This earthing point should have a low impedance connection to the conductive enclosure of the apparatus

cabinet, or similar, where the unit is built-in. This conductive enclosure should be connected to the earthing

system of an installation and may be directly connected to the protective earth.