S2 dip-switch dte flow control, S2 dip-switch dtr handling, S2 dip-switch rs-485 control – Westermo IDW-90 User Manual

Page 21: Use stored values

Advertising
background image

21

6620-2200

S2 DIP-switch
DTE flow control

ON

1 2 3 4 5 6 7 8

Use stored values

ON

1 2 3 4 5 6 7 8

Hardware flow control
RTS/CTS AT&K3

ON

1 2 3 4 5 6 7 8

No flow control CTS is always ON,
RTS ignored AT&K0&R1

ON

1 2 3 4 5 6 7 8

Software flow control
XON/XOFF
CTS is always ON, RTS
ignored AT&K4&R1

ON

1 2 3 4 5 6 7 8

No flow control CTS follows DTR,
RTS ignored AT&K0 &R2

ON

1 2 3 4 5 6 7 8

Software flow control
XON/XOFFCTS fol-
lows DTR, RTS ignored
AT&K4&R2

ON

1 2 3 4 5 6 7 8

No flow control CTS follows changes
on RTS AT&K0&R0

ON

1 2 3 4 5 6 7 8

Software flow control
XON/XOFF
CTS follows
RTS AT&K4

S2 DIP-switch
DTR handling

ON

1 2 3 4 5 6 7 8

Use stored values

ON

1 2 3 4 5 6 7 8

DTR is evaluated:
Dropping the DTR line
by the DTE will discon-
nect an existing ISDN
connection.An incoming
call will be accepted only
with DTR active. AT&D2
or AT**cdtr = 2

ON

1 2 3 4 5 6 7 8

DTR is evaluated:
Ignored. AT&D or AT**cdtr = 0

ON

1 2 3 4 5 6 7 8

DTR is evaluated:
Incoming calls will be
accepted independent of
DTR status; DTR drop
disconnects an active
connection. AT&D4 or
AT**cdtr = 4

S2 DIP-switch
RS-485 control

ON

1 2 3 4 5 6 7 8

RS-232 enable
RS-422/485 disable

ON

1 2 3 4 5 6 7 8

RS-422/485 4 wire
enable RS-232 disable

ON

1 2 3 4 5 6 7 8

RS-485 2 wire enable
RS-232 disable

S2: 8 not used