Westermo IDW-90 User Manual

Page 34

Advertising
background image

34

6620-2200

… Frequently used settings for PLC-systems

ISDN

Network

Most PLC-systems and other industrial applications where modems are used, require the
same changes to default settings.
The most commonly encountered problems concern speed, parity and control signals
from the connected equipment.
Speed and parity are changed with the switches under the cover in block S1. If this action
does not solve the problem the modem’s answering codes and possible echoing of com-
mands might be the source of the difficulty.
Below follows a list of commands that might resolve the problems. The commands may of
course be placed on one single command line if desired.

Configure the IDW-90 connected to the PLC

AT&F0

Set the unit to factory default

ATV0

Gives the answering codes in short format. (digits)

ATQ1

No result codes are sent on the RS-232/V.24 connection.

ATE0

Commands that are sent from the terminal/computer etc. are not echoed
back to the RS-232/V.24 connection.

AT&C1

DCD will follow the carrier on the line.

AT&K0

No handshaking.

at**dabort=0

Character abort option OFF

AT&W

Save settings