Space, Power supply, Accessories – H3C Technologies H3C SR6600-X User Manual
Page 16

6
Space
•
For ease of installation and maintenance, make sure that the front and rear clearances are at least
1 m (3.28 ft).
•
For heat dissipation, make sure the headroom in the equipment room is no less than 3 m (9.84 ft),
and an appropriately sized air conditioner is provided.
Power supply
Perform the following steps to satisfy the power supply requirements of the SR6602-X routers:
1.
Calculate the system power consumption.
The system power consumption of the SR6602-X routers depends on the number and type of interface
modules, and fan tray power consumption. For the power consumption of the router, see “
Chassis views and technical specifications
2.
Select power modules according to the system power consumption.
To ensure normal operation of the router, make sure the maximum output power of the power modules is
greater than the system power consumption of the router. After determining the system power
consumption, you can select power modules as needed. For power module specifications, see
“
Appendix A Chassis views and technical specifications
.”
3.
Check that the power source on the installation site satisfies the power input of the power modules.
Make sure the power source of the installation site is steady and can satisfy the input requirements
of the power modules and parameters such as rated voltage.
Accessories
Console cable
(supplied with
router)
3 m (9.84 ft)
grounding cable
(supplied with
router)
Rear mounting
bracket (supplied
with router)
Front mounting
bracket and cable
management
bracket (supplied
with router)
Load-bearing screw
(supplied with
router)
Rubber feet
(supplied with
router)
M6 screw
(user-supplied)
Cage nuts
(user-supplied)
ESD-preventive wrist
strap (user-supplied)
Cable tie
(user-supplied)