4  Product Description

SMA Solar Technology AG

14

SSMxx-21-IA-BS-JP-en-20

Installation Manual

4.3 DC Load-Break Switch

The Sunny String-Monitor can be disconnected on the inverter side by means of a DC load-break switch. Use of the DC

load-break switch is only permissible if LV/HRC fuses with gPV characteristic are installed upstream in the inverter or the

main DC distribution box.

If a string fails, the current difference in the above example is 4.5 A which equates to a deviation of 90% from the mean

value. Assuming that the settings in the above example remain unaltered, i.e. tolerance at 10% and tripping time at

10 minutes, the error sum of 20% will already be reached after the first query interval of 5 minutes. The data logger

now issues an SMU warning.