Connecting the Connector to the String-Monitor Unit

• Plug the connector with the connected data cables into the pin

connector of the lowest String-Monitor Unit.

6.7.3 Connecting the Data Cable in the SSMxx-21-BS-JP

The Sunny String-Monitors must be connected to the RS485 communication bus and supplied with voltage.
The RS485 data cables and the voltage supply are connected jointly in one data cable to terminals -X712 and -X713

by means of a connector. This means that two data cables will be connected to each Sunny String-Monitor. Only one

data cable is connected and terminated at the last Sunny String-Monitor.

Figure 15: Connection of Sunny String-Monitors to the RS485 communication bus (example)

Procedure:
To connect the data cables in the Sunny String-Monitor, carry out the following steps in the given sequence. The exact

procedure is described in the following sections.

• Preparing the data cables
• Connecting the data cables to the connectors
• Connecting the connectors in the Sunny String-Monitor

Limited number of String-Monitor Units per Ethernet hub
Since the String-Monitor Unit measurement PCBs are supplied with voltage via the data cables, the number of

connected String-Monitor Units is limited.

• Do not connect more than ten String-Monitor Units per Ethernet hub.

The various types of Sunny String-Monitors are equipped with differing numbers of String-Monitor Units:

• Sunny String-Monitor SSM8-21: 1 String-Monitor Unit
• Sunny String-Monitor SSM16-21: 2 String-Monitor Units
• Sunny String-Monitor SSM24-21: 3 String-Monitor Units