2 ssm8-21-bs-jp/ssm16-21-bs-jp, 4 connecting the string cables – SMA SSM8-21-BS User Manual

Page 26

Advertising
background image

6  Electrical Connection

SMA Solar Technology AG

26

SSMxx-21-IA-BS-JP-en-20

Installation Manual

6.3.2 SSM8-21-BS-JP/SSM16-21-BS-JP

The features of the Sunny String-Monitor are dependent on the order option. The maximum configuration of the

Sunny String-Monitor is shown in the overview diagrams.

Figure 11: Connections (with the SSM16-21-BS-JP as an example)

6.4 Connecting the String Cables

SMA Solar Technology AG recommends using bootlace ferrules for connecting the string cables to the fuse holders.

Cable requirements:

☐ PV1-F cable must be available.
☐ Conductor cross-section of the string cable for connection of one string cable to the fuse holders: 0.75 mm

2

to

16 mm

2

Position

Designation

A

Terminals for string cables, positive terminal

B

Terminal for data cables

C

Terminal for DC main cable, positive terminal

D

Grounding cable connection

E

Terminal for DC main cable, negative terminal

F

Terminals for string cables, negative terminal