SMA SSM8-21-BS User Manual

Page 53

Advertising
background image

SMA Solar Technology AG

12  Technical Data

Installation Manual

SSMxx-21-IA-BS-JP-en-20

53

Sealing range of cable glands M40

13 mm to 32 mm

Maximum width of the terminal lugs when connecting two

cables per potential

55 mm

Suitable connection material

Copper/aluminum

Number of cables per potential

1/2

DC Main Connection to Terminals*

* Terminals available as accessories

Type of terminal

V-box terminal

Maximum conductor cross-section

300 mm

2

Suitable connection material

Copper/aluminum

Number of cables per potential

1/2

Cable gland

M40

Sealing range of cable gland

13 mm to 32 mm

Connection of String Cables to Fuse Holder
Conductor cross-section for one string cable per fuse holder

0.75 mm

2

to 16 mm

2

Cable feed-through plate

M50

Clamping range of cable entry plate

5.0 mm to 10.5 mm

Ground Connection in SSMxx-21-BS
Terminal

Surge arrester

Conductor cross-section

16 mm

2

Cable gland

M25

Sealing range of cable gland

8 mm to 17 mm

Ground Connection in SSMxx-21-BS-JP
Terminal

Screw terminal

Conductor cross-section

16 mm

2

Cable gland

M25

Sealing range of cable gland

8 mm to 17 mm

Surge Arrester for Communication and Voltage Supply in SSMxx-21-BS-JP
Type

BLITZDUCTOR

®

BVT ALD 60

Arrester class

Type1P1

Nominal voltage

60 V

DC

D1 Lightning surge current (10/350) total

5 kA

C2 nominal discharge current (8/20) total

20 kA

Test standards

IEC 61643-21/EN 61643-21

DC Main Connection to Busbar

Advertising
This manual is related to the following products: