6 related parameters, 6related parameters – Yaskawa 1000 Series Drive Option - CANopen Installation User Manual

Page 21

Advertising
background image

YASKAWA ELECTRIC TOBP C730600 45B 1000-Series Option SI-S3 Installation Manual

21

6 Related Parameters

6

Related Parameters

The following parameters are used to set up the drive for operation with the option.

Confirm proper setting of the all parameters in

Table 4

before starting network

communications.

Table 4 Related Parameters

No.

Name

Description

Default

b1-01

<1>

Frequency Reference
Selection

Selects the frequency reference input source
0: Operator - Digital preset speed d1-01 to d1-17
1: Terminals - Analog input terminals
2: MEMOBUS/Modbus communications
3: Option card
4: Pulse Input (Terminal RP)

<2>

b1-02

<1>

Run Command Selection

Selects the run command input source
0: Digital Operator - RUN and STOP keys
1: Digital input terminals S†
2: MEMOBUS/Modbus communications
3: Option card

1

E2-04

<3>

Motor 1 Motor Poles

Set the number of motor poles described on the
motor nameplate.
2 to 48

4

F6-01

Operation Selection after
Communications Error

Determines drive response when a bUS error is
detected during communications with the
CANopen Option
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<4>

1

F6-02

External Fault Detection
Conditions (EF0)

Sets the condition for external fault detection
(EF0)
0: Always detected
1: Detected only during operation

0

F6-03

Stopping Method for
External Fault from
Communication Option
Board

Determines drive response for external fault input
(EF0) detection during CANopen communication
0: Ramp to Stop
1: Coast to Stop
2: Fast-Stop
3: Alarm Only

<4>

1

F6-06

<5>

Torque Reference/Torque
Limit selection from
Communications Option

0: Torque reference/torque limit via network

communications are disabled.

1:

Torque reference/torque limit via network

communications are enabled.

<6>

0

F6-07

NetRef/ComRef Selection
Function

0: Multi-step speed reference disabled (F7 mode)
1: Multi-step speed reference allowed (V7 mode)

0