background image

4 Option Components

12

YASKAWA ELECTRIC TOBP C730600 42C 1000-Series Option SI-P3 Installation Manual

Table 5 LED Operation After Power-up Diagnostic

{

: On /

: Flashing /

z

: Off

LED

Communication

Status

Possible Cause

Solution

RUN ERR COMM BF

No power

Drive has no power.

Check all wiring to the drive, then
turn on the power.

Option is not properly
connected to the drive or is
not receiving enough power.

Shut off the drive and make sure
the option is connected properly.
Turn the power back on.

• Checking

connection with
the drive

• Waiting for data

from the master

• Option is reading the node

address or parameter
configuration.

• Waiting for initial input

data from master device.

Option self-
diagnostics error

The option is damaged.

Cycle power to the drive. If the
LED status does not change,
replace the option.

Problem
connecting to the
drive

• Problem initializing the

drive and the option.

• Incorrect node address.

• Cycle power to the drive. If the

LED status does not change,
replace the option.

• Check the node address setting in

the drive (F6-10).

Waiting for data
from the master
device

Waiting for data from the
master device.
(Set_Parm_Message or
Chk_Cfg_Message)

• Check master network settings.
• Make sure the master device is

operating normally.

• Check the terminal resistance

settings on the data line.

• Check for problems with the data

line and connector.

• Check if the data line is

connected properly to
communication connector CN5.

Incorrect data or
option time out
waiting for data

The communication settings
in the master are set
incorrectly.

Check the communication settings
in the master.

Sending or
receiving data