5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 42C 1000-Series Option SI-P3 Installation Manual

23

Cable Requirements

Table 6 Communication Cable Requirements

Cable Length

Communication speed determines maximum permissible cable length.

Table 7

shows the

specifications for Type A bus cables.

Table 7 Communication Cable Length

GSD Files

To facilitate network implementation, obtain a GSD file from one of the following websites

depending on your region:
U.S.: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: Contact your Yaskawa representative.

Condition

Specifications

Impedance

135 to 165

Ω at a frequency of (3 to 20 MHz)

Capacity

30 pF/m maximum

Loop Resistance

110

Ω/km maximum

Core Cross-Section

0.34 mm

2

minimum

Core Diameter

0.64 mm minimum

Communication Speed (kbps)

Distance per Segment

9.6

1200 m (3937 ft.)

19.2

1200 m (3937 ft.)

45.45

1200 m (3937 ft.)

93.75

1200 m (3937 ft.)

187.5

1000 m (3280 ft.)

500

400 m (1312 ft.)

1500

200 m (656 ft.)

3000

100 m (328 ft.)

6000

100 m (328 ft.)

12000

100 m (328 ft.)