8 troubleshooting, Drive-side error codes, 8troubleshooting – Yaskawa 1000 Series Drive Option - Profibus-DP Installation User Manual

Page 30

Advertising
background image

30

YASKAWA ELECTRIC TOBP C730600 42C 1000-Series Option SI-P3 Installation Manual

8 Troubleshooting

8

Troubleshooting

Drive-Side Error Codes

Table 13

lists the various fault codes related to the option. Further details on various faults

can be found in the drive Technical Manual.

Faults

Both bUS (Option Communication Error) and EF0 (External Fault Input from the option)

can appear as either an alarm or as a fault. When a fault occurs, the digital operator ALM

LED remains lit. When an alarm occurs, the digital operator ALM LED flashes.
Check the following items first when an error code occurs on the drive:

• Communication cable connections

• Make sure the option is properly installed to the drive

• Operation status of the controller program and controller CPU

• Did a momentary power loss interrupt communications?

Table 13 Fault Displays, Causes, and Possible Solutions

Digital Operator Display

Fault Name

bUS

Option Communication Error
The connection was lost after establishing initial communication.
Only detected when the run command frequency reference is assigned to the option
(bl-01 = 3 or bl-02 = 3).

Cause

Possible Solution

Master controller (PLC) has
stopped communicating.

Check for faulty wiring.
Correct any wiring problems.

Communication cable is not
connected properly.

A data error occurred due to
noise.

• Counteract noise in control circuit wiring, main circuit lines, and ground wiring.
• If a magnetic contactor is the noise source, install a surge absorber to the

contactor coil.

• Use cables recommended by Yaskawa or another type of shielded line. Ground

the shield on the controller side and on the option side.

Option is damaged.

If there are no wiring problems and the error continues to occur, replace the option.

Digital Operator Display

Fault Name

EF0

External Fault Input from the option
The alarm function for an external device has been triggered.

Cause

Possible Solution

An external fault is being sent
from the main controller (PLC).

• Remove the cause of the external fault.
• Reset the external fault input from the PLC device.

Problem with the PLC program. Check the program used by the PLC and make the appropriate corrections.