7 Option Data and I/O Maps

28

YASKAWA ELECTRIC TOBP C730600 42C 1000-Series Option SI-P3 Installation Manual

Table 12 Extended Data 2 Register Map

20

MEMOBUS/Modbus Data 1 High Byte

20

MEMOBUS/Modbus Data 1 High Byte

21

MEMOBUS/Modbus Data 1 Low Byte

21

MEMOBUS/Modbus Data 1 Low Byte

22

MEMOBUS/Modbus Data 2 High Byte

22

MEMOBUS/Modbus Data 2 High Byte

23

MEMOBUS/Modbus Data 2 Low Byte

23

MEMOBUS/Modbus Data 2 Low Byte

24

MEMOBUS/Modbus Data 3 High Byte

24

MEMOBUS/Modbus Data 3 High Byte

25

MEMOBUS/Modbus Data 3 Low Byte

25

MEMOBUS/Modbus Data 3 Low Byte

26

MEMOBUS/Modbus Data 4 High Byte

26

MEMOBUS/Modbus Data 4 High Byte

27

MEMOBUS/Modbus Data 4 Low Byte

27

MEMOBUS/Modbus Data 4 Low Byte

28

Reserved

28

Reserved

29

29

30

30

31

Handshaking Register

31

Handshaking Register

<1> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7).

<2> Set when network communication is designated as the source of the torque limit and torque reference

(F6-06 = 1).When enabled, d5-01 determines whether the value is read as the torque limit value (d5-01 = 0) or

read as the torque reference value (d5-01 = 1). In CLV/PM, this value is read as the torque limit.

<3> To select drive analog output channel for communications, set H4-01 (Multi-Function Analog Output Terminal

FM) and H4-04 (Multi-Function Analog Output Terminal AM) to 000 (through-mode).

<4> Drive digital output ON/OFF during communications, set H2-01 (Terminal M1, M2 and MC Function Selection

(relay)), H2-02 (Terminal P1 Function Selection (open-collector)), and H2-03 (Terminal P2 Function Selection

(open-collector)) to F (through-mode).

<5> Unit depends on the setting of o1-03 (Digital Operator Display Scaling). Input data is 0 when the drive is set for

V/f Control or OLV/PM.

<6> Not possible when using V/f control, V/f with PG, or OLV/PM (A1-02 = 0, 1, or 5).

<7> Data is displayed in units of 0.01 A for drives 7.5 kW and smaller, and in units of 0.1 A for drives 11 kW and

larger. The number of decimal places in the parameter value depends on the drive model and the ND/HD selection

in parameter C6-01. For delails, refer to the 1.3 Model Number and Nameplate Check of the drive Technical

Manual.

Output (Master Device to Drive)

Input (Drive to Master Device)

Byte

Description

Byte

Description

0

Operation Command High Byte

0

Drive Status High Byte

1

Operation Command Low Byte

1

Drive Status Low Byte

2

Frequency Reference High Byte

2

Motor Speed High Byte

<1>

3

Frequency Reference Low Byte

3

Motor Speed Low Byte

<1>

4

MEMOBUS/Modbus Function Code

4

MEMOBUS/Modbus Function Code

5

MEMOBUS/Modbus Starting Register
Address High Byte

5

MEMOBUS/Modbus Starting Register
Address High Byte

6

MEMOBUS/Modbus Starting Register
Address Low Byte

6

MEMOBUS/Modbus Starting Register
Address Low Byte

Output (Master Device to Drive)

Input (Drive to Master Device)

Byte

Description

Byte

Description