6 related drive parameters – Yaskawa EtherNet/IP User Manual

Page 26

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

F7-15

(03F3)

Communication Speed

Selection

Sets the communication speed

10: 10 Mbps

100: 100 Mbps

101: 10 (Port 1)/100 Mbps (port 2)

102: 100 (Port 1)/10 Mbps (port 2)

Default: 10

Range: 10; 100 to
102

<10>

F7-16

(03F4)

Communication Loss

Timeout

Sets the timeout value for communication loss detection in

tenths of a second. A value of 0 disables the connection

timeout.

Example: An entered value of 100 represents 10.0 seconds.

Default: 0.0

Min.: 0.0

Max.: 30.0

F7-17

(03F5)

EtherNet/IP Speed

Scaling Factor

Sets the scaling factor for the speed monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-18

(03F6)

EtherNet/IP Current

Scaling Factor

Sets the scaling factor for the output current monitor in

EtherNet/IP Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-19

(03F7)

EtherNet/IP Torque

Scaling Factor

Sets the scaling factor for the torque monitor in EtherNet/

IP Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-20

(03F8)

EtherNet/IP Power

Scaling Factor

Sets the scaling factor for the power monitor in EtherNet/

IP Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-21

(03F9)

EtherNet/IP Voltage

Scaling Factor

Sets the scaling factor for the voltage monitor in EtherNet/

IP Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-22

(03FA)

EtherNet/IP Time

Scaling

Sets the scaling factor for the time monitor in EtherNet/IP

Class ID 2AH Object.

Default: 0

Min.: -15

Max.: 15

F7-23 to

F7-32

(03FB to

0374)

Dynamic Output

Assembly Parameters

Parameters used in Output Assembly 116. Each parameter

contains a MEMOBUS/Modbus address. The value

received for Output Assembly 116 will be written to this

corresponding MEMOBUS/Modbus address. A

MEMOBUS/Modbus address value of 0 means that the

value received for Output Assembly 116 will not be written

to any MEMOBUS/Modbus register.

Default: 0

F7-33 to

F7-42

(0375 to

037E)

Dynamic Input

Assembly Parameters

Parameters used in Input Assembly 166. Each parameter

contains a MEMOBUS/Modbus address. The value sent for

Input Assembly 166 will be read from this corresponding

MEMOBUS/Modbus address. A MEMOBUS/Modbus

address value of 0 means that the value sent for Input

Assembly 166 is not defined by the user, therefore the

option default register value will be returned.

Default: 0

<1>

To start and stop the drive with the EtherNet/IP master device using serial communications, set b1-02 to 3 or
set the “Net Control” bit in the assemblies or Control Supervisor Object. To control the drive frequency reference
of the drive via the master device, set b1-01 to 3 or set the Net Reference bit in the assemblies or AC/DC Object.

<2>

When set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as installing
an emergency stop switch.

6 Related Drive Parameters

26

YASKAWA TOEP YAICOM 16A 1000-Series Option Dual-Port EtherNet/IP SI-EN3D Installation Manual

Advertising