Extended Speed Control Input - 71 (0x47)

Input

Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

71

0

0

At

Speed

Ref

from

Net

Ctrl

from

Net

Ready

Running

2 (REV)

Running

1

(FWD)

Warning Faulted

1

Drive State

1

2

Speed Actual (Low Byte)

3

Speed Actual (High Byte)

Name

Description

Faulted

Faulted

0: No Faults Occurred

1: Fault Occurred

Warning

Warning

0: No Warning Occurred

1: Warning Occurred

Running 1 (FWD)

Forward Running

0: Stop or Reverse Running

1: Forward Running

Running 2 (REV)

Reverse Running

0: Stop or Forward Running

1: Reverse Running

Ready

Drive Ready

0: Not Ready

1: Ready

Ctrl from Net

Status of Run command from Network

0: Run command is not from network

1: Run command is from network

Ref from Net

Status of Speed reference from Network

0: Speed reference is not from network

1: Speed reference is from network

At Speed

Speed Agree

0: No Speed Agree

1: Speed actual at speed reference

Drive State

Contains the value from the Control Supervisor (Class 0x29) Instance 1 Attribute 6.

Speed Actual

Actual Drive Speed

Monitors drive output frequency.

Speed actual data: Output frequency x 2

SS

(SS: Speed scale)

Setting range: 0 to 0xFFFF

For example, when output frequency of 1024 with a speed scale of 2:

Speed actual data = 1024 x 2

2

= 4096 = 0x1000

Unit depends on o1-03.

9 Input Assemblies (Drive Produces)