6 Related Parameters

22

YASKAWA ELECTRIC TOBP C730600 52C 1000-Series Option PG-E3 Installation Manual

F1-04

(383)

PG Deviation
Operation
Selection

0: Ramp to stop (decelerates at time set to C1-02)
1: Coast to stop
2: Fast Stop (decelerates at the time set to C1-09)
3: Continue running
NOTICE: Due to potential damage to the motor and
machinery, do not use the "Continue running" setting
except under special circumstances.

CLV
CLV/PM

Default:

<1>

Range: 0 to 3

F1-05

(384)

PG 1 Rotation

0: Forward = A pulse leads
1: Forward = B pulse leads

CLV
CLV/PM

Default:

<1>

Range: 0, 1

F1-06

(385)

PG 1 Ratio for
PG Pulse
Monitor

Sets the division ratio for pulses output from the PG
encoder. Set as a three-digit number: x is the first
digit, y is the second digit, and z is the third digit:
When using the PG-E3 option card, the drive
disregards the value set for "x", and uses the formula
1/yz to determine the division rate for the pulse
generator. The setting range is consequently 1/32 to
1.

CLV
CLV/PM

Default: 1
Min: 1
Max: 132

F1-08

(387)

PG Overspeed
Level

Sets the level for detecting overspeed as a percentage
of the maximum output frequency.

CLV
CLV/PM

Default: 115
Min: 0
Max: 120

F1-09

(388)

Overspeed Det.
Time

Sets the time required for the motor to exceed the
level set in F1-08 to trigger a fault.

CLV
CLV/PM

Default: 0.0
Min: 0.0
Max: 2.0

F1-10

(389)

Excessive
Speed
Deviation Det.
Level

Sets the degree of speed deviation to trigger a dEv
fault. Set as a percentage of the maximum output
frequency.

CLV
CLV/PM

Default: 10
Min: 0
Max: 50

F1-11

(38A)

Excessive
Speed
Deviation Det.
Time

Sets the time required a speed deviation situation to
trigger a fault.

CLV
CLV/PM

Default: 0.5
Min: 0.0
Max: 10.0

F1-14
(38D)

PG Disconnect
Det. Time

Sets the time in seconds for PG encoder disconnect to
be detected.

CLV
CLV/PM

Default: 2.0
Min: 0.0
Max: 10.0

F1-18

(3AD)

Reverse
Rotation Det.
for PG 1

0: Disabled
n: Number of times a dv3 situation must be detected
to trigger a fault.

CLV/PM

Default: 10
Min: 0
Max: 10

F1-19

(3AE)

Reverse
Rotation Det.
for PG 1

0: Disabled
n: Number of times a dv4 situation must be detected
to trigger a fault.

CLV/PM

Default: 128
Min: 0
Max: 5000

F1-20

(3B4)

PG 1 Hardware
Disconnect

0: Disabled. No fault if the connection is lost.
1: Enabled. Fault if connection is lost.

CLV
CLV/PM

Default: 1
Range: 0, 1

No.

(Addr. Hex)

Name

Description

Available

Control

Mode

Values

Advertising