Table 8 Operation Error Displays, Causes, and Possible Solutions

Digital Operator Display

Fault Name

oPE02

Parameter Range Setting Error
Use U1-18 to find parameters set outside range.

Cause

Possible Solution

Parameters were set outside the
possible range.

Set parameters to the proper values.

Note: When multiple errors occur at the same time, other errors

are given precedence over oPE02.

Digital Operator Display

Fault Name

oPE06

Control Method Selection Error
Correct the setting for the control method.

Cause

Possible Solution

Control mode requires installing
a PG option, but no PG option is
installed (A1-02 = 7).

• Connect a PG option.
• Correct the value set to A1-02.