Peripheral communications protocol (pcp) – Yaskawa VS-616G5 InterBus-S Control Card SI-R User Manual

Page 11

Advertising
background image

VS-616G5 Option Instruction Manual: InterBus-S Control Card SI-R

Page 11

Peripheral Communications Protocol (PCP)

The PCP channel supports three objects:

The SI-R board uses one-word PCP channel communications. The board supports only
up to four cycles per PCP communication. In other words, the PCP communication
message can only be up to four words long.

Object 6800 (Acceleration Time 1)

Using this parameter the IBS master can read and write ACCELERATION TIME
1 in the inverter. The object is accessed with PCP service read or write parame-
ter.

Object 6801 (Deceleration Time 1)

Using this parameter the IBS master can read and write DECELERATION TIME
1 in the inverter. The object is accessed with PCP service read or write parameter.

Table 7: Output Data: Inverter Status

Bit No.

Description

0

Running

1

Zero speed

2

Reverse running

3

Reset command receiving

4

Speed agree

5

Inverter ready

6

Minor fault

7

Major fault

8

OPE error

9

During momentary power ridethrough

A

Local/Remote

B

Terminal 9-10 output

C

Terminal 25 output

D

Terminal 26 output

E

Motor selection

F

Zero servo completion (FV control mode only)

ID

Name

Data type

Access

6800 (HEX)

ACCELERATION

16 bit integer

R/W

6801 (HEX)

DECELERATION

16 bit integer

R/W

6802 (HEX)

MODBUS COMMAND

ARRAY (3 x 16 bit integer)

R/W