Yaskawa VS-616G5 InterBus-S Control Card SI-R User Manual

Page 13

Advertising
background image

VS-616G5 Option Instruction Manual: InterBus-S Control Card SI-R

Page 13

Examples of using Modbus PCP on SI-R

A. Read value of inverter torque reference:

Parameter U1-09, address 28 hex

Send message:

Word1 = 0003 (read)
Word2 = 0028 (U1-09 address 28h)
Word3 = 0000 (no data)

Receive message:

Word1 = 0003 (read resp)
Word2 = 0028 (U1-09 data)
Word3 = 03E8 (100.0% value)

B. Actual fast cycle data of example above:

Inverter is running forward at 30.00Hz

Word0

Word1

Word2

Word3

Sending

1st message

0000

0001

0bb8

6802

2nd message

0000

0001

0bb8

0003

3rd message

0000

0001

0bb8

0028

4th message

0000

0001

0bb8

0000

Receiving

1st message

0000

2C31

0bb8

6802

2nd message

0000

2C31

0bb8

0003

3rd message

0000

2C31

0bb8

0028

4th message

0000

2C31

0bb8

03E8

For complete details on Modbus communication with the VS-616G5, please
contact your nearest Yaskawa representative and ask for Document # PI95029,
Modbus Communication.

Write fault

22H

Parameters are changed during running or undervoltage condition.

23H

Write parameter during undervoltage.

24H

Write parameter during calculating parameter.

Using the Phoenix Contact PCPM Software
A printed example of how to use the SI-R InterBus-S communication card with the Phoenix
Contact PCPM software program is available from Yaskawa Electric America, Inc. If you
require this document, please contact your local Yaskawa representative and ask for Document
# SI98001 PCPM S ft

f

th SI R