Interbus-s function, Fig. 7 interbus-s topology – Yaskawa VS-616G5 InterBus-S Control Card SI-R User Manual

Page 8

Advertising
background image

Page 8

VS-616G5 Option Instruction Manual: InterBus-S Control Card SI-R

INTERBUS-S FUNCTION

InterBus-S System Description

The following contains a brief technical and functional description of the InterBus-S
standard. For a more detailed description, please consult the InterBus-S specification.

InterBus-S Remote Bus Data

The remote bus bridges large distances within the system. The entire remote bus can
be up to 12.8 km in length (from the host to the last connected remote bus module).
This is achieved by dividing the entire remote bus into individual segments.

A remote bus segment consists of the transmission line (remote bus cable), and the bus
module connected to it; a remote bus segment can bridge up to 400 m. The complete
remote bus can thus be subdivided into 256 remote bus segments.

Host
(Master)

BK module

for local

bus

Local I/O

Local I/O

Local I/O

BK module

for installation

bus

Installation remote bus

Remote

bus

device

Remote

bus

device

Remote

bus

device

Control Cabinet

Local Bus

Fig. 7 InterBus-S Topology

Remote bus
segment 1

Remote bus
segment 2

Remote bus
segment 3

Remote bus
segment 4

Remote bus
segment 5

Segment A

Segment B

Segment C

Each segment (1, 2, 3, 4, or 5) length

400m

Total segment (1 + 2 + 3 + 4 + 5)

2Km

Maximum 256 segments with total length < 12.8Km

Notes: