Introduction – Yaskawa VS-616G5 InterBus-S Control Card SI-R User Manual
Page 3

VS-616G5 Option Instruction Manual: InterBus-S Control Card SI-R
Page 3
INTRODUCTION
The InterBus-S Control Card SI-R is used to connect the VS-616G5 inverter to an InterBus-S network. It
can communicate with either 4-word fast cycle data or 3 objects in PCP (Peripheral Communications Pro-
tocol). These objects are: Accel Time 1, Decel Time 1, and Modbus commands. The communication rate
is fixed at 500 kbps with RS-422 electrical interface.
Table 1: InterBus-S Control Card SI-R Overview
Name
YEA Code Number
Functions
InterBus-S
Control Card
SI-R
YAG5-IBS
• Connects inverter to, and communicates with, an InterBus-S communication network
.
• Option card plugs into 2CN connector on the control board.
• Option card is a 4-word InterBus-S remote bus slave unit. PCP is supported.
• The card requires VS-616G5 Flash # VSG101042 or higher.
BUS IN
BUS OUT
connector
connector
Indication LEDs
Fig. 1 InterBus-S Control Card SI-R
(JP1)
(JP2)
Grounding lead wire
(connect to terminal #12
of inverter control board)
(Qty: 6)
YAG5-IBS T20143
Ver 1.1
3225B