VS-616G5 Option Instruction Manual: InterBus-S Control Card SI-R

Related-Parameters

Notes:

*

EF0:

External Fault Signal from Serial Communication Option Card (SI-R).
Operation Signal Bit 8.

** BUS:

Serial Communication Error between Serial Communication Option Card (SI-R) and PLC.

***F9-05:

Torque Reference/Limit Selection:
Due to Torque Reference/Limit, cannot be set via SI-R option parameter F9-05. MUST
be set to “0” (Torque Reference/Limit from option disabled) when control method is set to
“Flux Vector Control” (A1-02 = 3).

Parameter

Number

Name

Description

Factory

Setting

b1-01

Frequency Reference Selection

0: Digital Operator
1: Terminal
2: Serial Communication
3: Option (Frequency Reference comes from SI-R option

card.

1

b1-02

Operation Method Selection

0: Digital Operator
1: Terminal
2: Serial Communication
3: Option (Run Command comes from SI-R option card)

1

F9-01

EF0* Contact Mode Selection

0: Fault at “1”
1: Fault at “0”

0

F9-02

EF0 Detection Mode Selection

0: Always detected
1: Only detected while in operation

0

F9-03

EF0 Stop Method Selection

0: Ramp to stop according to C1-02 setting
1: Coast to stop
2: Ramp to stop according to C1-09 setting (fast-stop)
3: Operation continues, alarm only

1

F9-04

Trace Sample Time

This parameter has no effect on SI-R card

0

F9-05

***

Torque Reference/Limit Selection

Flux Vector Control Mode Only:
0: Torque Reference/Limit from option disabled
1: Torque Reference/Limit from option enabled

1

F9-06

BUS** Stop Method Selection

0: Ramp to stop according to C1-02 setting
1: Coast to stop
2: Ramp to stop according to C1-09 setting (fast-stop)
3: Operation continues, alarm only

1