6 related drive parameters – Yaskawa Modbus TCP/IP SI-EM3D User Manual

Page 27

Advertising
background image

<5>

The setting specifies that the Torque Reference or Torque Limit is to be provided via network communications
(F6-06 = 1). The motor may rotate if no torque reference or Torque Limit is supplied from the PLC.

<6>

Parameter setting value is not reset to the default value when the drive is initialized.

<7>

Cycle power for setting changes to take effect.

<8>

When F7-13 is set to 0, parameters F7-01 to F7-12 must be set, and all IP Addresses (as defined with parameters
F7-01 to F7-04) must be unique.

<9>

When F7-14 is set to 0 or 2, parameter F7-15 must be set.

<10>

Setting range differs depending on drive software version. PRG: 1020 and earlier, Range: 0 to 2
PRG: 1021 and later, Range: 0 to 8

<11>

Setting range differs depending on drive software version. PRG: 1020 and earlier, Range: 10, 100
PRG: 1021 and later, Range: 10; 100 to 102

Table 5 Option Monitors

No.

Name

Description

Value Range

U6-80

to

U6-83

Online IP Address

IP Address currently available; U6-80 is the most significant

octet

0 to 255

U6-84

to

U6-87

Online Subnet

Subnet currently available; U6-84 is the most significant octet 0 to 255

U6-88

to

U6-91

Online Gateway

Gateway currently available; U6-88 is the most significant

octet

0 to 255

U6-92 Online Speed

Link Speed

10: 10 Mbps

100: 100 Mbps

U6-93 Online Duplex

Duplex Setting

0: Half, 1: Full

U6-94 Port 2 Speed

Port 2 Link Speed

0: Half, 1: Full

U6-95 Port 2 Duplex

Port 2 Duplex Setting

10: 10 Mbps

100: 100 Mbps

U6-96 RSTP

RSTP Role and State

0000 to 9292

U6-98 First Fault

First Option Fault

U6-99 Current Fault

Current Option Fault

6 Related Drive Parameters

YASKAWA TOEP YAICOM 18A 1000-Series Option Dual-Port Modbus TCP/IP SI-EM3D Installation Manual

27

Advertising