B Parameter Table

188

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

H5: MEMOBUS/Modbus Serial Communication

Note: The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.

No.(Addr.)

Name

Description

Setting

H5-01

(425H)

<14>

<14> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.

Drive Node Address

Selects drive station node number (address) for MEMOBUS/Modbus terminals
R+, R-, S+, S-. Cycle power for the setting to take effect.

Default: 1
Min: 0
Max: FF

H5-02

(426H)

Communication Speed
Selection

0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.

Default: 3
Min: 0
Max: 8

H5-03

(427H)

Communication Parity
Selection

0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.

Default: 0
Min: 0
Max: 2

H5-04

(428H)

Stopping Method After
Communication Error (CE)

0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only

Default: 3
Min: 0
Max: 3

H5-05

(429H)

Communication Fault
Detection Selection

0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault will
occur.

Default: 1
Min: 0
Max: 1

H5-06

(42AH)

Drive Transmit Wait Time

Sets the wait time between receiving and sending data.

Default: 5 ms
Min: 5 ms
Max: 65 ms

H5-07

(42BH)

RTS Control Selection

0: Disabled. RTS is always on.
1: Enabled. RTS turns on only when sending.

Default: 1
Min: 0
Max: 1

H5-09

(435H)

Communication Fault
Detection Time

Sets the time required to detect a communications error. Adjustment may be
needed when networking several drives.

Default: 2.0 s
Min: 0.0 s
Max: 10.0 s

H5-10

(436H)

Unit Selection for
MEMOBUS/Modbus
Register 0025H

0: 0.1 V units
1: 1 V units

Default: 0
Min: 0
Max: 1

H5-11

(43CH)

Communications ENTER
Function Selection

0: Drive requires an Enter command before accepting any changes to parameter
settings.
1: Parameter changes are activated immediately without the Enter command.

Default: 0
Min: 0
Max: 1

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_