Yaskawa L1000E AC Drive CIMR-LE†A User Manual

Page 75

Advertising
background image

4 Start-Up Programming

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

75

St

ar

t-

Up

Pr

og

ra

m

m

in

g

4

T2-06: PM Motor Rated Current

Enter the PM motor rated current in amps.

T2-08: Number of PM Motor Poles

Enter the number of motor poles.

T2-09: PM Motor Base Speed

Enter the motor rated speed in r/min.

Note: T2-09 will be displayed when in CLV/PM.

T2-10: PM Motor Stator Resistance

Enter the motor stator resistance per motor phase.

T2-11: PM Motor d-Axis Inductance

Enter the d axis inductance per motor phase.

T2-12: PM Motor q-Axis Inductance

Enter the q axis inductance per motor phase.

T2-13: Induced Voltage Constant Unit Selection

Selects the units used for setting the induced voltage coefficient.

Setting 0: mV (r/min)
Setting 1: mV (rad/sec)

Note: If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor

Induction Voltage Constant 1) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-24 to 0.0.

No.

Parameter Name

Setting Range

Default

T2-06

PM Motor Rated Current

10% to 200% of the drive

rated current.

Depending on o2-04

No.

<1> When PG-E3 option connected: Max setting = 48

Parameter Name

Setting Range

Default

T2-08

Number of PM Motor Poles

2 to 120

<1>

6

No.

Parameter Name

Setting Range

Default

T2-09

PM Motor Base Speed

0 to 24000 r/min

150 r/min

No.

Parameter Name

Setting Range

Default

T2-10

PM Motor Stator Resistance

0.000 to 65.000

Ω

No.

Parameter Name

Setting Range

Default

T2-11

PM Motor d-Axis Inductance

0.00 to 600.00 mH

No.

Parameter Name

Setting Range

Default

T2-12

PM Motor q-Axis Inductance

0.00 to 600.00 mH

No.

Parameter Name

Setting Range

Default

T2-13

Induced Voltage Constant Unit Selection

0, 1

1

Advertising