B Parameter Table

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

211

Pa

ra

me

te

r T

abl

e

B

U2-06

(85H)

Motor Speed at Previous
Fault

Displays the motor speed at the previous fault.

No signal output
available

0.01%

<31>

U2-07

(86H)

Output Voltage at
Previous Fault

Displays the output voltage at the previous fault.

No signal output
available

0.1 Vac

U2-08

(87H)

DC Bus Voltage at
Previous Fault

Displays the DC bus voltage at the previous fault.

No signal output
available

1 Vdc

U2-09

(88H)

Output Power at Previous
Fault

Displays the output power at the previous fault.

No signal output
available

0.1 kW

U2-10

(89H)

Torque Reference at
Previous Fault

Displays the torque reference at the previous fault.

No signal output
available

0.1%

U2-11

(8AH)

Input Terminal Status at
Previous Fault

Displays the input terminal status at the previous fault. Displayed as in U1-10.

No signal output
available

U2-12
(8BH)

Output Terminal Status at
Previous Fault

Displays the output status at the previous fault. Displayed as in U1-11.

No signal output
available

U2-13
(8CH)

Drive Operation Status at
Previous Fault

Displays the operation status of the drive at the previous fault. Displayed as in
U1-12.

No signal output
available

U2-14
(8DH)

Cumulative Operation
Time at Previous Fault

Displays the cumulative operation time at the previous fault.

No signal output
available

1 h

U2-15

(7E0H)

Soft Starter Output at
Previous Fault

Displays the run speed after a soft start when a previous fault occurred.
Displayed as in U1-16.

No signal output
available

0.01%

<31>

U2-16

(7E1H)

Motor q-Axis Current at
Previous Fault

Displays the q-axis current for the motor at the previous fault. Displayed as in
U6-01.

No signal output
available

0.1%

U2-17

(7E2H)

Motor d-Axis Current at
Previous Fault

Displays the d-axis current for the motor at the previous fault. Displayed as in
U6-02.

No signal output
available

0.1%

U2-20

(8EH)

Heatsink Temperature at
Previous Fault

Displays the temperature of the heatsink when the most recent fault occurred.
Displayed as in U4-08.

No signal output
available

1

°C

U2-21

(7E6H)

Peak Hold Current
during Fault

Displays the peak current that occurred just prior to the previous fault.

No signal output
available

0.01 A

U2-22

(7E7H)

Peak Hold Frequency
during Fault

Displays the output frequency when the peak current displayed in U2-21
occurred.

No signal output
available

0.01 Hz

<10> The display resolution depends on the rated output power of the drive. Models 2A0018 to 2A0041 and 4A0009 to 4A0023 display values in

0.01 A units, while models 2A0059 to 2A0432 and 4A0030 to 4A0260 display values in 0.1 A units.

<31> Setting units are determined by the digital operator display unit selection (o1-03). When o1-03 = 0, the value is set in Hertz. When o1-03 = 4 or

5, the value is displayed in m/s. When o1-03 = 6, the value is displayed in ft/min.

<40> When checking the values of U1-03, U2-05 and U4-13 with the digital operator they are displayed in units of amperes, but when they are

checked using MEMOBUS communications, the monitor value in MEMOBUS communications is: displayed numeric value / 8192

× drive’s

rated current (A), from the condition “8192 (maximum value) = drive’s rated current (A)”.

No.

(Addr.)

Name

Description

Analog Output

Level

Unit

common

_

CLV

CLV/PM

V/f

OLV

All Modes

common

_

All Modes

common

_

All Modes

common

_

common

_

CLV

CLV/PM

V/f

OLV

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

All Modes

common

_

common

_

CLV

CLV/PM

V/f

OLV

common

_

CLV

CLV/PM

V/f

OLV

All Modes

common

_

All Modes

common

_

All Modes

common

_