Terminal configuration, Yea_common, 3 electrical installation – Yaskawa L1000E AC Drive CIMR-LE†A User Manual

Page 45

Advertising
background image

3 Electrical Installation

YASKAWA TOEPYAIL1E01A YASKAWA AC Drive L1000E Quick Start Guide

45

El

ec

tr

ical

I

n

st

al

la

ti

o

n

3

Terminal Configuration

Control circuit terminals are arranged as shown in

Figure 25

.

Figure 25

Figure 25 Control Circuit Terminal Arrangement

Wire Size and Torque Specifications

WARNING! Fire hazard. Tighten all terminal screws to the specified tightening torque. Loose electrical connections could result in

death or serious injury by fire due to overheating of electrical connections. Improperly tightened terminal screws can also cause

erroneous equipment operation.

Select appropriate wire type and gauges from

Table 14

. For simpler and more reliable wiring, use crimp ferrules on the

wire ends. Refer to

Table 15

for ferrule terminal types and sizes.

Table 14 Wire Gauges and Torque Specifications

Terminal

Block

Terminal

Size

Tightening

Torque

N m

(lb.in.)

Bare Wire Terminal

Ferrule-Type Terminal

Applicable

Wire Size

mm

2

(AWG)

Recomm.

mm

2

(AWG)

Applicable

Wire Size

mm

2

(AWG)

Recomm.

mm

2

(AWG)

Wire Type

TB1, TB2,
TB4, TB5,
TB6

FM, AC, AM, P1,
P2, PC, SC, A1,
A2, A3, +V, -V,
S1-S8, MA, MB,
MC, M1, M2, HC,
H1, H2, DM+,
DM-, IG, R+, R-,
S+, S-, RP, MP, E
(G)

M2

0.22 to 0.25

(1.9 to 2.2)

Standard wire:

0.25 to 1.0

(24 to 17)

Solid wire:

0.25 to 1.5

(24 to 16)

0.75

(18)

0.25 to 0.5

(24 to 20)

0.5

(20)

Shielded wire,

etc.

E(G) HC H1

H2 DM+ DM- IG

R+

R-

S+

S-

S1

S2

S3

S4

S5

S6

S7

S8

SN SC SP

V+ AC

V-

A1

A2 FM AM AC

P1

C1

C2

P2

M3 M4

M6

MA MB MC

M1 M2 M5

YEA_common